4
Set-up procedure
The panel must be set up after it has been connected.
The set up procedure will be exited automatically if no key is pressed for more than a minute,
or by pressing the on/off key.
Always start the set up procedure from the beginning, even if only one setting has to be
changed!
Setting the 'Maximum tank level' .
• Hold the float in the FULL position.
• Press the
key once.
• Press the
key.
Explanation:
- Float sensor:
- Ultrasonic sensor: hold the sensor close to a reflective surface.
16
090427.02
• Switch on the power.
Is the 'ON' LED on?
Ignore all other LEDs.
NO
• Press the
key once.
• Press and hold the
hold the float in the highest position.
Note: The sensor must be held steady in this
position for approx. 10 seconds.
key for approx. 10 seconds.
Make sure that an
ultrasonic sensor has been
calibrated; see 'Installation
instructions SENSORA'
090429.01, 'Calibration' .
A
Continue on the next page.
vetus® Waste water control panel WWCP
YES
• Press the
key to
bypass setting
the 'Maximum
tank level' .
OR