2. Select keyswitch function.
The GRAFIK Eye
QS control unit will display a
®
prompt to change your keyswitch's function (type).

Keyswitch

Change type?
Press OK
OK
Press the OK button on the QS control unit to
display the current keyswitch function/type. To
change, use the master buttons to scroll through
the available choices until the function you want
displays on the info screen.
Press the OK button to accept and save your
highlighted choice.
Change type?

Scene

OK
Occupant Copy
Programming
The next step is to configure your keyswitch to
specify which GRAFIK Eye QS control unit or
window treatment "listens" when the keyswitch
"talks" (depending on your keyswitch's
function). You will perform only one of Steps
3a through 3d for each keyswitch.
3a. For keyswitches with scene, panic, sequence,
Master
afterhours, sensor, or timeclock functions:
buttons
Press and hold the top button on the GRAFIK Eye
QS control unit lighting column until its LEDs flash
OK
in unison. Repeat for each control unit you want to
button
"listen" to the keyswitch for the selected function.
Note: To stop a control unit from "listening" to a
Master
buttons
Proceed to Step 4.
OK
button
5
1
2
3
4
5
6
Press and hold the top button on the lighting column
for 5 seconds to make control unit "listen".
keyswitch, put the keyswitch in setup mode,
and press and hold for 5 seconds the bottom
button on the lighting keypad of the control unit
you want to stop listening. The LEDs will stop
flashing.
1
2
3
4
5
6
OK
Press and hold
the bottom
OK
button for 5
seconds to make
control unit stop
"listening".
Installation Instructions