Commissioning; Addressing The Device; Operating The Alarm Led; Commissioning Of The Safe Bus Node Ue3212 - SICK UE3212 Instrucciones De Servicio

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

Operating instructions
UE3212
6

Commissioning

WARNING
8010726/TF84/2010-07-20
Subject to change without notice
Commissioning
Commissioning requires a thorough check by qualified safety personnel!
Before you operate, for the first time, a system protected by an AS6Interface Safety at Work
system in connection with a safety component connected, make sure that the system is
first checked and approved by qualified safety personnel.
Test the protective device after any changes!
The entire protective device must be tested for correct operation after each change.
6.1

Addressing the device

So that the safe bus node UE3212 can be identified in the AS6Interface network, it must
be assigned a unique free address. The address space is 1 to 31. As supplied the address
is set to 0.
The address can be set in the following ways:
Addressing using the cable addressing device SICK ASI6PM2 (6022426; the addressing
device SICK ASI6PM1 is not suitable for setting the address of the safe bus node
UE3212). The address of the safe bus node UE3212 can be set in conjunction with the
FKE base using addressing socket FKE6A (cf. chapter 9.2 "Accessories") via the
addressing cable ASI6PM26DSL1 (6022464) in mounted and wired state.
Addressing using the infrared addressing device ASI6PM2 (6022426) and the IR
addressing cable ASI6PM26DSL2 (6022465); prior to setting the address, stop all
communication in the safe bus node UE3212.
Automatic setting of the address by the AS6Interface master on the replacement of the
device.
6.2

Operating the ALARM LED

The safe bus node UE3212 has a red ALARM LED that can be programmed as required
using the output bit D0 on the AS6Interface network control. The LED illuminates when the
bit is set. It is thus, e.g., possible to display locally the triggering of the switching contact
connected.
Bit D1...D3 have no function.
6.3

Commissioning of the safe bus node UE3212

Using the LEDs check whether the device is ready for use. If the green LED (voltage
supply) is on and the red LED (FAULT display) is off, the device is ready for operation.
6.4

Commissioning of the system

Completely verify the safety functions of the entire system.
Fully document the configuration of the entire system, the individual devices and the
result of the safety check.
© SICK AG • Industrial Safety Systems • Germany • All rights reserved
GB
Chapter 6
95

Publicidad

Tabla de contenido
loading

Tabla de contenido