Model
#
CEM304
B
C
CEM365
B
C
CEM456
B
C
*For solid surface countertop installations, use maximum cutout dimensions and consult surface manufacturer for
specific cutting instructions.
Power Requirements
Installation Procedure
Seal with Foam Tape
Minimum Inches / (mm)
19-7/8" / (505 mm)
28-3/4" / (731 mm)
19-7/8" / (505 mm)
34-3/4" / (883 mm)
19-7/8" / (505 mm)
43-3/4" / (1111 mm)
Power Supply is dual rated: 240 Volts or 208 Volts, 3 wire, 60 Hz, with the following
circuit breaker requirements:
•
Model CEM304: 30 Amp circuit breaker
•
Model CEM365: 40 Amp circuit breaker
•
Model CEM456: 50 Amp circuit breaker
•
All Models: 240 Volt, 3 Wire, 60 Hz / 208 Volt, 3 Wire, 60 Hz
Install a junction box (not supplied), below the counter top within 3 feet (91.4 cm) of
flexible conduit (supplied) located at the right rear corner of the cooktop rough-in
box. Plan the installation of the unit so that the location of the junction box is within 3
feet (91.4 cm) of the right rear of the cooktop bottom. It must be accessible from the
front of the cabinet.
Figure 3 - Junction Box Installation
(approx 3 ft.(91.4 cm))
WARNING:
To avoid electrical shock hazard, before installing the cooktop, switch
power off at the service panel and lock the panel to prevent the power
from being switched on accidentally.
A foam tape is provided to seal the cooktop edges to the countertop. Turn cooktop
upside down and apply tape approximately 1/16" (1.6 mm) from the glass edges.
Use tape around the entire glass perimeter. Cut off excess tape where tape ends
butt.
20" / (508 mm)
28-7/8" / (734 mm)
20" / (508 mm)
34-7/8" / (886 mm)
20" / (508 mm)
43-7/8" / (1114 mm)
Conduit
12"
(30.4 cm)
(approx)
"j" Box
Maximum Inches / (mm)
English 3