ROUGH-IN
PLATE
TABS ON
BACK EDGE
SLOTS
OF PLATE
HEX NUTS (2)
7.
Engage two TABS on BLOWER / MOUNTING PLATE AS-
SEMBLY into two SLOTS in ROUGH-IN PLATE. Secure
blower / mounting plate assembly to THREADED STUDS
on rough-in plate with (2) 10-24 HEX NUTS.
(2) SCREWS
8.
Install the CALIBRATION BUTTON ASSEMBLY using (2)
SCREWS (provided).
9.
Plug one of the rough-in plate power cords into the control
box power cord.
10. Plug BLOWER POWER CORD and ROUGH-IN PLATE
POWER CORD into HOOD RECEPTACLES.
11. Wrap excess wires with wire ties (provided) to prevent contact
with blower wheel.
HOOD
RECEPTACLE
STUDS
ROUGH-IN
PLATE
POWER
CORD
HOOD
RECEPTACLE
BLOWER
POWER
CORD
BLOWER /
MOUNTING
PLATE
ASSEMBLY
CALIBRATION
BUTTON
ASSEMBLY
CALIBRATE iQ BLOWER
SYSTEM
INTERNAL BLOWER DUCTED UNITS ONLY
After the hood is installed and wired, engage the calibration
process (our Guaranteed Performance System Technology to
ensure full-rated airflow is being delivered). Prior to calibration,
ensure that all filters, light bulbs and duct system are installed.

CALIBRATION PROCESS

Hold the calibration button for 3 seconds; calibration button
will light up and stay on for up to 13 minutes. The blower will
start and begin the calibration process. When calibration is
complete, one of two things will occur:
1. The blower turns off and calibration button light stays on =
Successful calibration. Press the button to turn off the LED.
Note: The LED will also turn off if you select any blower
speed on the control.
2. The blower turns off and calibration button light blinks
continuously = Too much restriction in the ductwork is
preventing the IQ Blower System™ from achieving the rated
airflow. The blower is automatically set to maximum intensity.
NOTE: Common items that cause restrictions: restricted
damper flap (backdraft damper, wall cap, roof cap), too
many elbows, duct size less than 80% of hood outlet, poor
transition, use of flex ducting and/or crushed ducting.
Three options are available if your hood system has too
much restriction:
1. Accept airflow as is.
a. Press the calibration button to accept airflow as is. The
IQ Blower System™ is now configured to the highest
possible performance. The blinking calibration light
goes out. Note: The LED will also turn off if you select
any blower speed on the control.
2. Correct duct restriction, clear the original calibration data,
and repeat the calibration process.
a. Correct the duct restriction.
b. Clear the original calibration data by holding calibration
button for 10 seconds. The light will blink 3 times to
confirm and the blower configuration will go back to
default settings.
c. Repeat calibration process from the beginning.
3. Clear calibration data to reset hood to default factory
setting and achieve standard high pressure blower
performance.
a. Clear calibration data and reset hood to factory default
setting by holding calibration button for 10 seconds.
The light will blink 3 times to confirm and the blower
configuration will go back to default settings.
MODEL iQ12
Page 4