SPECIFICATIONS
Power supply
Liquid temp. range
Discharge size
Sump basin
NOTICE: Read this Owner's Manual for installation, operation, and safety information.
INSTALLATION
NOTICE:
Install pump on a hard, level surface (cement, asphalt, etc.). Never place pump directly on earth, clay or
gravel surfaces.
Piping – Sewage Applications (2"or Less Solids)
In any case, piping must not be smaller than pump discharge. When installed in a sewage system, pipe must be capable
of handling semi-solids of at least 2" (5.1 cm) diameter. The rate of flow in the discharge pipe must keep any solids
present in suspension in the fluid. To meet minimum flow requirements, the minimum pipe size is 2".
Use a 2" (5.1 cm) swing check valve in pump discharge to prevent backflow of liquid into sump basin. Check valve
should be a free flow valve that will easily pass solids.
NOTICE:
For best performance of check valve when handling solids, do not install it with discharge angled more than
45° above the horizontal. Do not install check valve in a vertical position as solids may settle in valve and prevent
opening on start up.
Drill a 1/8" (3.2mm) hole in discharge pipe about 1"-2" (2.5 -5.1cm) above quick connector. The hole must be in the
sump.
PIPE QUICK CONNECTION:
1. Insert 2in. discharge pipe (1) with vent hole into the quick connector (2).
Hand tighten the knurling nut of the quick connector as tight as possible.
4
SWW05002TPK/ SWW05002VPK:115V, 60 HZ., 15 Amp Circuit
SWW07503TPK/SWW05001TPK/SWW05001VPK/SWW07501TPK/SWW07501VPK:
115V, 60 HZ., 20 Amp Circuit
32-131° F (0-55° C)
2" FNPT
Minimum 18 in. (457 mm) diameter, 24 in. (609 mm) depth (For SWW07503TPK
SWW05001VPK SWW07501VPK SWW05001TPK SWW07501TPK SWW05002TPK)
Minimum 14 in. (355 mm) diameter, 18 in. (457 mm) depth (For SWW05002VPK)
For Professional Technical Support call 1-844-242-2475