TECHNICAL DATA
TYPE
Thermal power – output
Fuel
Electrical supply
Motor
Capacitor
Ignition transformer
Pump
Absorbed electrical power
Burner with CE marking in conformity with EEC directives: EMC89/336/EEC, Low Voltage 73/23/EEC,
Machines 98/37/EEC and Efficiency 92/42/EEC.
The burner meets protection level of IP 40, EN 60529.
1 – Return line
2 – Suction line
3 – Gauge connection
4 – Pump pressure regulator
5 – Vacuum gauge connection
6 – Hydraulic jack with air-damper
7 – Combustion head adjustment screw
8 – Lock-out lamp and reset button
9 – Flange with insulating gasket
10 – Start delaying device
2354
482T1
95 – 240 kW
–
Gas oil, max. viscosity at 20 °C: 6 mm
Single phase, 230 V ± 10%
Run current 1.5 A – 2750 rpm – 288 rad/s
5 µ F
Secondary 8 kV – 16 mA
Pressure 7 – 15 bar
0.33 kW
Fig. 1
S7332
EQUIPMENT
Quantity
2
1
4
1
1
1
1
GB
8 – 20 kg/h
2
/s
~
50Hz
Description
Flexible pipes with nipples
Flange with insulating gasket
Screws and nuts for flange
Hinge
Screw with two nuts for flange
Grommet
ENGLISH