mA Input FUNCTIONING DESCRIPTION
Rev 1.0
PROGRAMMING mA Input FUNCTIONING
Dosing proportional to the input current mA. The proportional range and the Flowrate %
can be freely decided.
The display shows on the first row the percentuage flowrate of dosing (80%= dosing during
240 seconds and stop dosing during next 60seconds) and on the second row the input
current measure of the pump (in figure is 14 mA)
Time base: 300 sec
PROGRAMMING:
Push and quickly release CAL button and scroll the menu using + and –
buttons till the display shows "Function Type". Push CAL to enter the
submenu and then by pressing + and – button choice " Function mA Input"
and confirm pressing CAL.
Push + and – button to choice the minimum current (mA Min) and confirm
by CAL .
Push + and – button to choice the percentuage of dosing Flowrate (Flow.
Min) of the pump when the input current is equal to mA Min. Confirm by
CAL .
Pushing + or – button choice if, when the current is lower than mA Min, the
pump has to dose (Yes) or not (No). Confirm by CAL .
Push + and – button to choice the maximum current (mA Max) and confirm
by CAL .
Push + and – button to choice the percentuage of dosing Flowrate
(Flow.Max) of the pump when the input current is equal to mA Max. Confirm
by CAL .
Pushing + or – button choice if, when the current is higher than mA Max, the
pump has to dose (Yes) or not (No). Confirm by CAL .
Push ESC button to esc the menu and go back in measure with the Pulse
functioning just programmed.