RECOMMENDED INSTALLATION FOR ALL APPLICATIONS
1. Electrical wiring and protection must be in accordance with governing
electrical codes.
2. Install proper combination union and check valve, preferably just above
the basin to allow easy removal of the pump for cleaning or repair.
If high head or below cover installation is required, use 30-0164 on
1-1/2" (DN40) pipe, 30-0152 on 2" (DN50) pipe and 30-0160 on 3" (DN80)
pipe.
3. All installations require a basin cover to prevent debris from falling into
the basin and to prevent injury.
4. When a check valve is installed, drill a 3/16" (5 mm) diameter hole in the
discharge pipe even with the top of the pump. NOTE: THE HOLE MUST
ALSO BE BELOW THE BASIN COVER AND CLEANED PERIODICALLY.
(High Head unit see "Caution" on front page). Water stream will be
visible from this hole when pump is operating.
5. Securely tape or clamp power cord to discharge pipe, clear of the float
mechanism(s).
6. Use a discharge pipe equivalent in diameter to the pump's discharge.

WIRING DIAGRAM

WIRING DIAGRAM
WHITE (1)
RUN CAP
MAIN WINDINGS
THERMAL PROTECTOR
Run Capacitor
400VAC
Two capacitors (25µF,400VAC)
in parallel.
Item #
HP
Voltage
5054-0004
1
BLACK (2)
RED (3)
START
WINDINGS
50µF
Hz
Amp
230
60
14
© Copyright 2021. All rights reserved.
7. Basin must be in accordance with governing codes and specifications.
8. Pump must be level and float mechanism(s) clear of sides of basin
before starting pump.
9. Basin must be clean and free of debris after installation.
10. Gate valve, shut-off valve, or ball valve to be supplied by installer and
installed according to any and all codes.
11. Locate float switches as shown in sketches. The best place for the "off"
point is above the motor housing and positioned 180° from the inlet.
Never put "off" point below discharge on pump.
12. Gas-tight seals are required to contain gases and odors.
13. Vent gases and odors to the atmosphere through vent pipe.
14. For proper spacing of "On" - "Off" switches refer to local or
national standards and guidelines.
15. Optional septic tank risers for easy access to pump, controls and filters.

PUMP PERFORMANCE CURVE

PERFORMANCE CURVE
120
36
110
100
30
90
80
24
70
60
18
50
40
12
30
20
6
10
0
10
20
GALLONS
LITERS
40
TOTAL DYNAMIC HEAD/FLOW
Feet
20
40
60
80
100
Shut-off Head
3
MODEL 5054
30
40
50
60
70
80
120
160
200
240
280
FLOW PER MINUTE
PER MINUTE
MODEL 5054
Meters
Gal.
Liters
6.1
70
265
12.2
69
261
18.3
68
257
24.4
51
193
30.5
21
81
114 ft. (35 m)