Installation Instructions for Optional Fixture Mounts
Overview of the Fixture Mounts
The optional fixture mounts are designed to replace the original
pendant mount on the explosion-proof light housing.
Wiring must comply with Article 500 of the National Electrical
Code and the local authority having jurisdiction.
For Marine applications, all wiring, including supply wire, must be
stranded wire and meet USCG (CFR46) Sections (110-113.)
Installing the CMXC-SB Ceiling Mount
To install the ceiling mount on the support surface:
1. See Figure 1. Secure the ceiling mount to the support surface
using the four external mounting slots.
EXTERNAL
MOUNTING SLOTS (4)
BLOCK SCREW (2)
2. Remove the terminal block from the ceiling mount by
removing the two screws securing it to the fixture.
3. For instructions on wiring the beacon, see page 8 for the
DC beacon or page 9 for the AC beacon.
Models CMXC-SB, PMXC-SB, and WMXC Series
6
Figure 1 Model CMXC-SB ceiling mount
THE CMXC-SB IS NOT SUITABLE FOR USE WITH
THROUGH-BRANCH CIRCUIT CONDUCTORS.
TERMINAL-
CLOSE-UP
PLUG
TERMINAL BLOCK
290A7243