Descargar Imprimir esta página

Lutron EcoSystem Guia De Instalacion página 3

Publicidad

Idiomas disponibles

Idiomas disponibles

EcoSystem
Step : EcoSystem Bus Supply and Enclosure Mounting
Note: Mount the EcoSystem Bus Supply in a location
where it can be easily located and accessed if servicing
or troubleshooting is necessary. The bus supply can be
mounted in any orientation (if required).
A. Select a UL-listed NEMA Type 1 (or better) electrical
enclosure with minimum dimensions of 8 in. x 8 in. x 4 in.
(203 mm x 203 mm x 102 mm) (l x w x d) or mount the
WM version using the mounting holes provided and skip
to Step 2. EcoSystem Bus Supply external dimensions are
shown in illustrations at right.
B. Mount UL-listed enclosure per enclosure's instructions.
C. Mount DIN rail (included with EcoSystem Bus Supply)
horizontally near the center of the enclosure.
D. Clip the EcoSystem Bus Supply onto DIN rail:
1. Hook the EcoSystem Bus Supply to the top of the DIN
rail
2. Using a screwdriver, pull the DIN rail clip out and away
from the DIN rail
3. Pivot the EcoSystem Bus Supply onto the DIN rail
4. Release the DIN rail clip
(The EcoSystem Bus Supply can be removed, if necessary,
by reversing this procedure.)
3
Clip EcoSystem Bus Supply onto DIN Rail
Lutron | 
| Bus Supply Installation Guide
TM
1
2
6 in. (152 mm)
0.25 in. (6.4 mm)
hole diameter
8 in.
(203 mm)
0.75 in. (19 mm)
knockouts for wiring
1 in. (25 mm)
8 in. (203 mm)
Mounting Holes & Dimensions of CS-L/2L-WM
A
B
Front View
C
Side View
A = 3.56 in. (85 mm)
B = 1.77 in. (45 mm)
C = 3.62 in. (92 mm)
Dimensions of CS-L/2L-CM (CS-L shown)
EcoSystem
4 in.
(102 mm)
1 in.
(25 mm)
typical
typical
E2 E2
E1
E1
C
B
Low voltage side
N
H/ L
H/ L
N
A
C
B
Line voltage side
 Bus Supply Installation Guide