Reference
Model
for
ordering
Alternating voltage output
C106
P01.1203.04
C116
P01.1203.16
C107
P01.1203.05
C117
P01.1203.17
C160
P01.1203.08
C173
P01.1203.09
4.3
Precision and dephasing
C100 / C102 / C103 / C106 / C107 : 1000 A calibre
Intensity in A~
Intrinsic error
(1)
Dephasing
C112 / C113 / C116 / C117 : calibre 1000 A
Intensity in A~
Intrinsic error
(1)
Dephasing
C122 / C148 : 1000 A calibre
Intensity in A~
Intrinsic error
(1)
Dephasing
C148 : 500 A calibre
Intensity in A~
Intrinsic error
(1)
Dephasing
C148 : 250 A calibre
Intensity in A~
Intrinsic error
(1)
Dephasing
(1) As % of output signal
(2) Unspecified
(3) + 0.1 mA for C100 / C102 / C103 or + 0.1 mV for C106 / C107
(4) + 5 µA for C112 / C113 or + 5 µV for C116 / C117
Nominal
measuring
scope
100 mA... 1000 A
10 mA... 1000 A
100 mA... 1000 A
10 mA... 1000 A
1 A... 1000 A
100 mA... 100 A
100 mA... 10 A
1 A... 1000 A
100 mA... 100 A
10 mA... 10 A
1 mA... 1 A
(in reference conditions)
0,1...10 A
10 A
≤ 3%
≤ 3%
(3)
≤ 3°
(2)
10...100 mA
0,1...1 A
≤ 3%
≤ 2%
(4)
(5)
(2)
(2)
1...20 A
20 A
≤ 5%
6%
(6)
≤ 5°
(2)
1...10 A
10 A
≤ 6%
6%
(7)
≤ 6°
(2)
1...5 A
5 A
≤ 10%
10%
(8)
(2)
(2)
12
Input/Ouput
Connection
ratio
1 mV~ / 1 A~
Sockets
1 mV~ / 1 A~
Lead
1 mV~ / 1 A~
Lead
10 mV~ / 1 A~
BNC
100 mV~ / 1 A~
1 mV~ / 1 A~
10 mV~ / 1 A~
Lead
100 mV~ / 1 A~
1000 mV~ / 1 A~
50 A
200 A
≤ 1,5%
≤ 0.75%
≤ 1.5°
≤ 0.75°
1...10 A
10...100 A
≤ 1%
≤ 0.5%
≤ 2°
≤ 1°
50 A
200 A
≤ 3%
≤ 1.5%
≤ 3°
≤ 1.5°
25 A
100 A
≤ 3%
≤ 2%
≤ 4°
≤ 3°
12,5 A
50 A
≤ 5%
≤ 2%
≤ 10°
≤ 10°
(5) + 3 µA for C112 / C113 or + 3 µV for C116 / C117
(6) + 0.5 mA
(7) + 1 mA
(8) + 2 mA
1000...1200 A
≤ 0.5%
≤ 0.5°
100...1200 A
≤ 0.3%
≤ 0.7°
1000...1200 A
≤ 1%
≤ 1°
500...600 A
≤ 1%
≤ 2.5°
250...300 A
≤ 2%