5.2 - EVA CONFIGURATION (using the NO auxiliary automatic solenoid valve)
The MTC10 controls valves V1 and V5.
The Burner Control controls valve V2.
The following checks are performed before starting the burner:
1. Leak test V1
2. Leak test V2 and V5
During the test, valve V5 discharges the gas to the outside in a safe place. After the test, the device waits for the signal
provided by the Burner Control. Once the signal is received, V1 on the valve control connector is opened (V5 is kept closed).
The Burner Control opens V2.
Valve Control
Madas Technical Manual - 9|9.4 - REV. 0 of 8
Electrical connections
23
Feb 2019
th
V1: NC safety solenoid valve
V2: NC work solenoid valve
V5: NO auxiliary valve
P:
Pressure switch
T:
Thermostat
LP: Minimum pressure switch
: Test volume
P
: Low pressure switch
1
P
: High pressure switch
2
MTC10