3
Mechanical installation
WARNING
•
During installation, comply with the following installation and safety instructions as well as the
additional instructions provided on the supplied CD.
•
Mount the devices with sufficient clearance to other components so that the cooling air will
circulate freely. Avoid soiling by grease and air pollution by dust, aggressive gases, etc.
•
Make sure, that no foreign particles (e.g. dust, metal shavings, wires, screws, tools) can get
inside the mains unit.
•
Install the mains unit on a non-flammable mounting plate.
•
Installation in bottom-up or horizontal position is not permissible.
GB
•
Screw the mains unit to a metallic (not varnished) mounting plate.
•
The mains unit must be earthed.
•
For potential equalization connect frequency inverters, cabinets, machine frames, filters etc. via
short conductors (with large cross- section) to the same earth potential.
AEC 401 Size 3 (9.7 to 15.2 kVA) and AEC 401 Size 4 (17.3 and 22.2 kVA)
b
b1
x
a1
x
28
a
a2
x
100 mm
Quick Start Guide AEC
c
c1
top M4x20
oben M4x20
Bottom M4x60
Screw fixing brackets to heat sink and
mounting plate.
06/13