AVAILABLE CONFIGURATIONS (PARAMETER P00)
027
 S ystem pipes: 4
 V alve: NO
 H eating element: NO
 S peeds: 3
 S ummer/winter switching logic: AIR
028
 S ystem pipes: 4
 V alve: NO
 H eating element: NO
 S peeds: 4
 S ummer/winter switching logic: LOCAL
029
 S ystem pipes: 4
 V alve: NO
 H eating element: NO
 S peeds: 4
 S ummer/winter switching logic: REMOTE
030
 S ystem pipes: 4
 V alve: NO
 H eating element: NO
 S peeds: 4
 S ummer/winter switching logic: AIR
031
 S ystem pipes: 4
 V alve: 2-3 WAYS
 H eating element: NO
 S peeds: 3
 S ummer/winter switching logic: LOCAL
032
 S ystem pipes: 4
 V alve: 2-3 WAYS
 H eating element: NO
 S peeds: 3
 S ummer/winter switching logic: REMOTE
033
 S ystem pipes: 4
 V alve: 2-3 WAYS
 H eating element: NO
 S peeds: 3
 S ummer/winter switching logic: AIR
034
 S ystem pipes: 4
 V alve: 2-3 WAYS
 H eating element: NO
 S peeds: 4
 S ummer/winter switching logic: LOCAL
035
 S ystem pipes: 4
 V alve: 2-3 WAYS
 H eating element: NO
 S peeds: 4
 S ummer/winter switching logic: REMOTE
FWEC3
Advanced plus electronic controller
FC66002765
036
 S ystem pipes: 4
 V alve: 2-3 WAYS
 H eating element: NO
 S peeds: 4
 S ummer/winter switching logic: AIR
037
 S ystem pipes: 4
 V alve: NO
 H eating element: YES
 S peeds: 3
 S ummer/winter switching logic: LOCAL
038
 S ystem pipes: 4
 V alve: NO
 H eating element: YES
 S peeds: 4
 S ummer/winter switching logic: LOCAL
CONFIGURATION OF DIGITAL OUTPUTS
(PARAMETERS P09,P10,P11,P12)
P09,P11
= 0
The digital output is not governed by the controller; the contact
is always open.
P09,P11
= 1
The contact status reflects the current operating mode (summer
or winter) of the unit.
P09,P11
= 2
The contact status indicates the operation mode of the unit:
cooling (summer) or heating (winter).
P09,P11
= 3
The contact status indicates that the unit is in cooling mode.
P09,P11
= 4
The contact status indicates that the unit is in heating mode.
P09,P11
= 5
The contact status indicates if the control in ON or OFF
P09,P11
= 6
The contact status indicates if an alarm is triggered (serious
or non-serious, see "Alarms")
P09,P11
= 7
The contact is used to switch ON/OFF any external device
for dehumidifying the air (cooling mode only). The ON/OFF
logic is based on a reading of the humidity in the room and
the SETPOINT selected with parameter
diagram shown:
P13
. It follows the
Air humidity
Installation and user manual
5