Installation
Neutral assembly (optional)
4×
Neutral assembly (EOHXSN78), optional
Install the neutral link on the bottom plate of the safety switch
to the existing threaded holes according to the picture. See
chapter Cabling.
EOHXSN78:
Wire range: (4) #2 - 600 kcmil / 4 x 35 -300 mm
Torque: wire tightening for Cu and Al cables 500 lbs.in / 55.7 Nm
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
See general safety instructions on page 1/2 before proceeding.
2
Failure to follow these instructions will result in death or serious injury.
Instruction Bulletin EOH367, EOH368, 1SCC340033M1401 / A | Installation 1/13
DANGER
1