Failure code
Digital tube
Indication
indication
on wired
on master
controller
unit
(hex)
Compression ratio
39-1
39-1
too high protection
Compression ratio
39-2
39-2
too low protection
High pressure
40
40
sensor Pd too high
protection
Discharging temp.
43
43
sensor Td too low
protection
Communication
46
46
with inverter board
failure
CT current is too
53
53
low or current
sensor fault
Valve plate module
54
54
communication
fault
Communication
failure between
valve plate
57
57
module and host
computer(sending
by valve plate)
Tc1 temp sensor
of valve plate
58
58
error(sending by
valve plate)
Tc2 temp sensor
of valve plate
59
59
error(sending by
valve plate)
Valve plate module
60
60
error(sending by
valve plate)
Valve plate module
61
61
error(sending by
valve plate)
Failure code
Failure description
definition
After compressor is running, compression ratio 8. for
continuous 5 minutes stop and alarm.2 minutes and 50
seconds later, resume automatically, if it occurs 3 times in
an hour, confirm the failure.
In normal operation, compression ratio <1.8 for continuous
5 minutes stop and alarm.2 minutes and 1 seconds later,
resume automatically, if it occurs 3 times in an hour, confirm
the failure.
In normal operation, Pd>=4.15Mpa for continuous 50ms,
alarm and stop. 2 minutes and 50 seconds later, resume
automatically, if it occurs 3 times in an hour, confirm the
failure.
In normal operation, if Td<CT+50°F
(10 ) for continuous 5 minutes, the unit stops and alarms.2
minutes and 50 seconds later, resume automatically. If it
occurs 3 times in an hour, confirm the failure. After fixed
frequency compressor alarms, inverter compressor will
continue to run. If fixed frequency compressor has been
locked for 3 times, the unit will stop and alarm.
No communication within 30 seconds continuously
3 minutes after recovery
Cannot receive valve plate module signal in 200 continuous
rounds or receive wrong data,recover automatically when
received right data.
Communication failure between valve plate module and
host computer
Tc1 temp. sensor cannot connect with valve plate module
Tc2 temp. sensor cannot connect with valve plate module
Reserved
Reserved
21
Remarks
Once
confirmation,
un-resumable
Once
confirmation,
un-resumable
Once
confirmation,
un-resumable
Once
confirmation,
un-resumable
Resumable
3 times in an
hour, confirm
failure; once
confirmation,
un-resumable
Resumable
Resumable
Resumable
Resumable
Resumable