Selecting Installation Site; General - Rotex RRLQ011CAV3 Manual De Instalación

Unidad exterior para bomba de calor de aire-agua
Ocultar thumbs Ver también para RRLQ011CAV3:
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 104
5.
S
ELECTING INSTALLATION SITE

5.1. General

CAUTION
Make sure to provide for adequate measures in order
to prevent that the outdoor unit be used as a shelter
by small animals.
Small animals making contact with electrical parts can
cause malfunctions, smoke or fire. Please instruct the
customer to keep the area around the unit clean.
Select an installation site where the following conditions are
satisfied and that meets with your customer's approval.
-
Places which are well-ventilated.
-
Places where the unit does not bother next-door neighbours.
-
Safe places which can withstand the unit's weight and
vibration and where the unit can be installed level.
-
Places where there is no possibility of flammable gas or
product leak.
-
The equipment is not intended for use in a potentially
explosive atmosphere.
-
Places where servicing space can be well ensured.
-
Places where the indoor and outdoor units' piping and wiring
lengths come within the allowable ranges.
-
Places where water leaking from the unit cannot cause
damage to the location (e.g. in case of a blocked drain pipe).
-
Places where the rain can be avoided as much as possible.
-
Do not install the unit in places often used as work place.
In case of construction works (e.g. grinding works) where a
lot of dust is created, the unit must be covered.
-
Do not place any objects or equipment on top of the unit (top
plate).
-
Do not climb, sit or stand on top of the unit,
-
Be sure that sufficient precautions are taken, in accordance
with applicable legislation, in case of refrigerant leakage.
When installing the unit in a place exposed to strong wind, pay
special attention to the following.
Strong winds of 5 m/sec or more blowing against the outdoor
unit's air outlet causes short circuit (suction of discharge air),
and this may have the following consequences:
-
Deterioration of the operational capacity.
-
Frequent frost acceleration in heating operation.
-
Disruption of operation due to rise of high pressure.
-
When a strong wind blows continuously on the face of the
unit, the fan can start rotating very fast until it breaks.
Refer to the figures for installation of this unit in a place where
the wind direction can be foreseen.
RRLQ011~016CAV3+W1
Outdoor unit for air to water heat pump
4PW57794-1 – 10.2010
Install a baffle plate on the air suction side of the outdoor unit
and set the outlet side at a right angle to the direction of the
wind:
2
1
Baffle plate
2
Strong wind
3
Discharge air
Prepare a water drainage channel around the foundation, to
drain waste water from around the unit.
If the water drainage of the unit is not easy, please build up the
unit on a foundation of concrete blocks, etc. (the height of the
foundation should be maximum 150 mm).
If you install the unit on a frame, please install a waterproof plate
within 150 mm of the underside of the unit in order to prevent the
invasion of water from the lower direction.
When installing the unit in a place frequently exposed to snow,
pay special attention to elevate the foundation as high as
possible.
If you install the unit on a building frame,
please install a waterproof plate (field
supply)(within 150 mm of the underside of
the unit) in order to avoid the drainwater
dripping. (See figure).
Make sure that the unit is installed level.
2
1
Installation manual
7

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Rrlq014cav3Rrlq016cav3Rrlq011caw1Rrlq014caw1

Tabla de contenido