7. COMMISSIONING

• Fill the device
- Open a hot water tank in the distribution system,
- Open the cold water tap on the safety unit, ensuring that the unit's drainage valve is
closed,
- After drawing from the hot water taps with no noise in the pipes, close the taps: your
EN
equipment is full.
• The immersion sleeves are fi tted to the surface in the factory with thermal contact paste
and do not need sealing.
• The thermometer should be fi tted in the immersion sleeve on the façade.
• Verifi cation of correct operation
- During heating, the water drips out of the safety unit drain hole (this hole should be
connected to the drain). This phenomenon is normal. The water expands as it is heated,
and the additional volume can reach 2 to 3% of the device's capacity.
- Check the watertightness of the pipe connection.
- Check that the hydraulic components are operating correctly by putting the safety unit in
the drainage position and the stop position and vice versa to eliminate any build-up.

8. MAINTENANCE

The device you have just purchased should provide satisfactory service for many years as
long as this advice is followed:
• IMPORTANT: put the safety unit in the drainage position at least once a month to
evacuate any deposits that can obstruct the safety unit's safety valve over time.
Failure to respect this maintenance rule can lead to the deterioration of the tank (not
covered by the warranty).
• Cleaning: once a year. The cleaning frequency should be adjusted according to the
quality of the fl uids stored (water hardness) and the volume of water consumed. A
lateral inspection cover or manhole is provided for cleaning. Replace the seals each time it
is disassembled.
Cover plate tightness:
Lateral fl ange and drainage fl ange: 8 Nm.
Manhole: 60 Nm.
• Tank cleaning: the drainage tube placed at the lowest point of the tank enables it to be
drained fully.
• Specialist maintenance: have the watertightness and operation of the safety unit safety
valve checked at least every year. The valve should begin to open at its set pressure and
allow full fl ow at an additional 0.5 bar.
• Anode: The anodes should be inspected every year and replaced when three quarters of
the magnesium has been consumed. If there is not enough headroom beneath the ceiling,
anodes are available in a chain version (refer to the specifi c anode manual).
For insulated versions, inspect for wear without removing the anode. The values are given
as a guide, and were produced for water with a conductivity of 500 μs/cm.