Electrical Connections - CREE LIGHTING ZR Serie Instrucciones De Instalación

Ocultar thumbs Ver también para ZR Serie:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

ELECTRICAL CONNECTIONS

NOTE: The emergency driver must be fed from
the same branch as the AC Driver.
STEP 1:
Using customer supplied 90°C minimum rated wire
connectors, make the following electrical connections:
a. Connect the black luminaire lead to the
unswitched voltage supply lead.
b. Connect the white/red luminaire lead to
the switched supply switched.
c. Connect white luminaire lead to the neutral supply lead.
d. Connect ground bare or green/yellow wire
lead to the supply ground lead.
e. If 0/1-10V Dimming is used, connect the violet lead
to the supply positive dimming lead. If dimming is
not being used ensure to cap off the violet lead.
f.
If 0/1-10V Dimming is used, connect the gray lead
to the supply negative dimming lead. If dimming is
not being used ensure to cap off the gray lead.
STEP 2:
Turn the ON/OFF switch on the side of the emergency driver to ON
status when installation is completed and AC power has been supplied.
See Figure 9.
NOTE: DO NOT put the switch on the side of the emergency driver to
ON until installation is complete and AC power is supplied
ON Switch
9
FCC NOTICE
CAUTION: Changes or modifications not expressly approved could void your authority to use this equipment.
This device complies with Part 15 of the FCC Rules. Operation to the following two conditions: (1) This device may not cause harmful interference, and (2)
this device must accept any interference received, including interference that may cause undesired operation.
This device has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are
designed to provide reasonable protection against harmful interference when the device is operated in a commercial environment. This device generates,
uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference
to radio communications. Operation of this device in a residential area is likely to cause harmful interference in which case the user will be required to
correct the interference at his own expense.
CAN ICES-005 (A)/NMB-005 (A)
© 2020 Cree Lighting, A company of IDEAL INDUSTRIES. All rights reserved. For informational purposes only. Content
is subject to change. See www.creelighting.com/warranty for warranty and specifications. Cree
registered trademarks of Cree, Inc. ZR14™, ZR22™ and ZR24™ are trademarks of Cree Lighting, A company of IDEAL
INDUSTRIES.
4 of 4
and the Cree logo are
®
LUMINAIRE
BARE OR
GREEN/YELLOW
GROUND
NEUTRAL
WHITE
WHITE
SWITCHED HOT
WHITE/RED
UNSWITCHED HOT
BLACK
DIM (+) VIOLET
VIOLET
DIM (-) GREY
GREY