Installation and Maintenance Instructions
•
WARNING: EXPLOSION HAZARD — Do not disconnect the equipment
unless power has been switched off or unless the area is known to be non-
hazardous.
WARNING: EXPLOSION HAZARD — Do not remove or replace the fuse
•
when energized.
Failure to follow all safety precautions and instructions may result in property
damage, serious injury, or death.
With respect to the potential electrostatic charging hazard as mentioned in the
certificate "Specific Conditions of Use", under normal conditions of use, these
devices are for fixed installations and not generally in contact with people.
The risk of ignition is low. In addition, maintenance, cleaning, and extreme
environmental factors (ex. high velocity dust laden atmospheres or high pressure
steam) should be taken into account by the end user, using local Explosive
Atmosphere (Ex) Electrical installations design, selection, inspection, and
maintenance Codes and Standards. Cleaning of the devices should only be
done with a damp cloth.
Certification
Certificate Nos.: ATEX Cert No.: Baseefa15ATEX0155X
Protection:
Standards:
Specific Conditions of Use:
1.
The Modular Audible Device enclosure incorporates a sinter and the
volume is greater than 100 cm
Device in carbon disulphide gas atmospheres is not permitted.
2.
The Modular Audible Device has external non-metallic surfaces which may
provide electrostatic charging hazard. See the manufacturer's instructions for
further information.
6
IECEx Cert No.: IECEx BAS 15.0104X
ATEX coding:
Ex db IIB T5 Gb or Ex db e IIB T5 Gb
Ex tb IIIC T100°C Db IP66
Ex db IIC T4 Gb or Ex db e IIC T4 Gb
Ex tb IIIC T135°C Db IP66
EN60079-0: 2012 +A11: 2013, EN60079-1: 2014,
EN60079-7: 2007, EN60079-31: 2014, IEC60079-0: 7th Ed.,
IEC 60079-1:6th Ed., IEC 60079-7: 4th Ed.,
IEC 60079-31:2nd Ed.
Model G-SPK Global Series Loudspeaker
II 2 G D
(Tamb = -55°C to + 49°C)
(Tamb = -55°C to + 70°C)
, therefore use of the Modular Audible
3