Air-to-water Heat Pump Split Versati
Outdoor unit
Model
GRS-CQ8.0Pd/NaE-K
GRS-CQ10Pd/NaE-K
GRS-CQ12Pd/NaE-K
GRS-CQ14Pd/NaE-K
GRS-CQ16Pd/NaE-K
GRS-CQ12Pd/NaE-M
GRS-CQ14Pd/NaE-M
GRS-CQ16Pd/NaE-M
Notes
(a) No additional charge of the refrigerant is need when the pipe length is less than 10m, if the pipe length is
longer than 10m, additional charge of the refrigerant is needed according to the table.
(b) Example: If 14kW model is installed at a distance of 25m, (25-10)x50=750g refrigerant should be added.
Rated capacity is based on standard pipe length and maximum allowable length is based on the product
reliability in the operation. Oil trap should be installed every 5-7 meters when the location of outdoor unit is
higher than indoor unit.
Copyright 2018. This translation is property of GREE PRODUCTS SL. All rights reserved. Total or partial reproduction without its express authorization is prohibited.
Indoor unit
A
B
Indoor unit
Pipe size
(Diameter:Φ)
gas
Liquid
Standard
5/8"
3/8"
5m
5/8"
3/8"
5m
5/8"
3/8"
5m
5/8"
3/8"
5m
5/8"
3/8"
5m
5/8"
3/8"
5m
5/8"
3/8"
5m
5/8"
3/8"
5m
28
Outdoor unit
Indoor unit
B
Outdoor unit
B
Length B
Elevation A
Max.
Standard
30m
0m
30m
0m
30m
0m
30m
0m
30m
0m
30m
0m
30m
0m
30m
0m
SPLIT
TYPE
A
Oil trap
A
Additional
refrigerant
Max.
15m
50g/m
15m
50g/m
15m
50g/m
15m
50g/m
15m
50g/m
15m
50g/m
15m
50g/m
15m
50g/m