Air-to-water Heat Pump Split Versati
18.4.2 Specification of power supply wire and leakage switch
Power cable specifications and Leakage switch types in the following list are recommended.
Model
GRS-CQ8.0Pd/NaE-K(O)
GRS-CQ10Pd/NaE-K(O)
GRS-CQ8.0Pd/NaE-K(I)
GRS-CQ10Pd/NaE-K(I)
GRS-CQ12Pd/NaE-K(O)
GRS-CQ14Pd/NaE-K(O)
GRS-CQ16Pd/NaE-K(O)
GRS-CQ12Pd/NaE-K(I)
GRS-CQ14Pd/NaE-K(I)
GRS-CQ16Pd/NaE-K(I)
GRS-CQ12Pd/NaE-M(O)
GRS-CQ14Pd/NaE-M(O)
GRS-CQ16Pd/NaE-M(O)
GRS-CQ12Pd/NaE-M(I)
GRS-CQ14Pd/NaE-M(I)
GRS-CQ16Pd/NaE-M(I)
Notes
(a) Leakage Switch is necessary for additional installation. If circuit breakers with leakage protection are in use,
action response time must be less than 0.1 second, leakage circuit must be 30mA.
(b) The above selected power cable diameters are determined based on assumption of distance from the
distribution cabinet to the unit less than 75m. If cables are laid out in a distance of 75m to 150m, diameter of
power cable must be increased to a further grade.
(c) The power supply must be of rated voltage of the unit and special electrical line for air-conditioning.
(d) All electrical installation shall be carried out by professional technicians in accordance with the local laws
and regulations.
(e) Ensure safe grounding and the grounding wire shall be connected with the special grounding equipment of
the building and must be installed by professional technicians.
(f) The specifications of the breaker and power cable listed in the table above are determined based on the
maximum power (maximum amps) of the unit.
(g) The specifications of the power cable listed in the table above are applied to the conduit-guarded multi-wire
copper cable (like, YJV XLPE insulated power cable) used at 40℃ and resistible to 90℃ (see IEC 60364-5-52).
If the working condition changes, they should be modified according to the related national standard.
(h) The specifications of the breaker listed in the table above are applied to the breaker with the working
temperature at 40℃ . If the working condition changes, they should be modified according to the related national
standard.
Copyright 2018. This translation is property of GREE PRODUCTS SL. All rights reserved. Total or partial reproduction without its express authorization is prohibited.
Leakage
Power Supply
Switch
V,Ph,Hz
220-240,~,50Hz
220-240,~,50Hz
380-415,3N~,50Hz
40
Minimum Sectional
Area of Earth Wire
2
(A)
(mm
)
20
3.3
20
3.3
50
13.3
50
13.3
30
5.3
30
5.3
30
5.3
50
13.3
50
13.3
50
13.3
25
3.3
25
3.3
25
3.3
20
3.3
20
3.3
20
3.3
SPLIT
TYPE
Minimum
Sectional Area
of Power Supply
Wire
2
(mm
)
2×3.3
2×3.3
2×13.3
2×13.3
2×5.3
2×5.3
2×5.3
2×13.3
2×13.3
2×13.3
4×3.3
4×3.3
4×3.3
4×3.3
4×3.3
4×3.3