Selection of the best location
Install the air conditioner in the location that satisfies the following conditions.
• The place shall easily bear a load exceeding four times the indoor unit's weight.
• The place shall be able to inspect the unit as the figure.
• The place where the unit shall be leveled.
• The place shall allow easy water drainage.
(Suitable dimension "H" is necessary to get a slope to drain as figure.)
• The place shall easily connect with the outdoor unit.
• The place where the unit is not affected by an electrical noise.
• The place where air circulation in the room will be good .
• There should not be any heat source or steam near the unit.
CAUTION : In case that the unit is installed near the sea, the installation parts
may be corroded by salt, The installation parts (and the unit) should be taken ap-
propriate anti-corrosion measures.
[Inspection Hole Standard]
Number of
inspection hole
1
2
Hole size should be more
than the size of IDU.
Top view
Inspection hole
(unit: inch)
(23.6 x 23.6)
Control box
23.6
Front view
Distance between
false ceiling & actual ceiling
More than 39.4 inch
7.9 inch to 39.4 ich
Less than 7.9 inch
23.6
Front
H
Remarks
Sufficient space in the ceiling for servicing.
Insufficient space. Difficult for servicing
Minimum height for motor replacement.
Installation
Installation Manual 9