PARAMETER
C8
C9
NOTE: Changes entered for timing values will be effective only after exiting the programming, while changes to
other variables will be immediately effective.
Please remember that eventual changes to the configuration parameters of the machine could negatively affect
its efficiency. Thus, changes have to be arranged in collaboration with the manufacturer.
IT'S FORBIDDEN TO MODIFY THE OTHER CONFIGURATION PARAMETERS OF THE ELECTRONIC CONTROLLER
WITHOUT THE SERVICE CENTER'S AUTHORIZATION AND COLLABORATION.

3.1.3 ANOMALY WARNING

The controller is capable to recognize certain types of anomalies to the drying circuit. In such cases, an alarm message
will blink on the display, alternated to the current dew – point value.
MESSAGE
(BLINKING)
High Dew – point value
HtA
Very high Dew – point value
Ht2
LtA
Interruption or short circuit on
PF1
the PTC probe input line
ESA
Energy saving mode activated
ES2
Series of alarms very close to
ASt
Note: PF1 has priority on all other alarm messages.
Cod. 710.0138.01.00 Rev1A – 04.2008
DESCRIPTION
Delay between condensate
discharges
Time required for condensate
discharge
WARNING FOR USER:
CAUSE
(delayed alarm)
(immediate alarm)
Low Dew – point value
each other
RANGE
1 ÷ 999 (min)
1 ÷ 999 (sec)
OUTPUTS
Alarm output ON
Refrig. Compressor output OFF
Fan output ON
Discharge cycle standard
Alarm output ON
Refrig. Compressor output OFF
Fan output OFF
Discharge cycle standard
Alarm output ON
Refrig. Compressor output OFF
Fan output OFF
Discharge cycle standard
Alarm output OFF
Refrig. Compressor output OFF
Fan output OFF
Discharge cycle standard
Alarm output ON
Refrig. Compressor output OFF
Fan output ON
Discharge cycle standard
SET VALUE
1
1 ÷ 3
ACTIONS
Resettable by switching off the
control board when dew-point
returns to preset range.
If it persists call our Service
Centre.
Automatic reset when dew-
point returns to preset range.
If it persists call our Service
Centre.
Resettable by switching off the
control board and replacing the
faulty probe.
Call our Service Centre.
No action necessary.
Automatic Reset
Call our Service Centre.
ENGLISH