45) -IT IS NOT RECOMMENDED AND DANGEROUS TO DELIVER HOT DOMESTIC SUPPLY WATER AT MORE THAN 42°C
-INSTANTANEOUS SHUT-OFF OF THE HOT WATER SUPPLY IN CASE OF ACCIDENTAL RUPTURE OF THE COLD WATER
SUPPLY ACCORDING NF EN1111.
46) MAINTENANCE OF THE THERMOSTATIC COMBINATION CARTRIDGE Ref. See general catalog
Cleaning or replacement
Disassembly:
-Close the water inlets.
-Remove the lever (See below).
-Remove, clean and reinstall as indicated.
47) Black line or point Ø 1.5 vertically aligned
48) Index on top
49) Stop 38°c
50) Vertical Flats
51) Reinstall the lever by keeping the mark (A) vertical
52) Maintenance
Replacing the solenoid valve Part no. See general catalogue
-Turn off the water inlet
-Remove the panel
53) Reassembly in reverse order
54) Replacing the Shower Grille Part number: 90185 (grille only) Part number: 90184 (grille + screw + limiter)
-Unscrewing expansion screw
-Replacement
55) Replacing the ''TOUCH'' control button Part no. See general catalogue
·Turn off the water inlet.
·Remove the panel
· Disconnect the wiring, remove the button.
· Reinstall in the reverse order to that of removal.
· Reinstall the panel, open the water inlet.
· Wait for 10 s, the panel is operational.
Commissioning
-Bleed the pipes
-Connect and open the shut-off valves fitted with filter seals
-Trigger several times to force the air out Weathering
-In case of installation in a freezing zone, the panel must be removed in winter Flow
-Delivered with a flow limiter 10 l/min
56) PROGRAMMING
3 operating parameters can be programmed:
Within 15 seconds after commissioning the parametes can be programmed
a) Flow time – Adjustable from 1 s to 5 min.
Preset to 30 s.
b) Automatic rinse frequency- Adjustable from 0 to 30 days in steps of 1 day.
Preset without mandatory flow.
c) Automatic rinse flow time– Adjustable from 15 s to 5 min in steps of 15 s.
Preset to 30 s.
57) Mini 10 s
58) Programming OK
59) a) Flow time delay
60) Flow programming activation
61) b) Drain frequency
62) Drain programming activation
63) day
64) c) Drain flow time
65) Mini 10 s
66) Drain flow time programming activation
67) Note: If we enter the programming procedure of each parameter and do not press anything to modify it, the default value is re-
adjusted.
68) This document is not contractual, we reserve the right to modify the characteristics of our products without notice.
69) PATENTED and REGISTERED MODELS - PRESTO production