Important Safety Instructions
SAVE THESE INSTRUCTIONS
This manual contains instructions and warnings that should be
followed during the installation, operation and storage of this
product. Failure to heed these instructions and warnings will void
the product warranty.
Important Warnings
• The PDU provides the convenience of multiple outlets, but DOES NOT provide surge or
line noise protection for connected equipment.
• The PDU is designed for indoor use only, in a controlled environment, away from
excess moisture, temperature extremes, conductive contaminants, dust or direct
sunlight.
• The PDU must be installed by a qualified technician only.
• Do not attempt to mount the PDU to an insecure or unstable surface.
• Install in accordance with National Electrical Codes. Be sure to use the proper over
current protection for the installation, in accordance with the plug rating/equipment
rating as follows:
Model
PDUV30HV
PDUMV30
PDUMV16HV, PDUMV20HV
PDUMV30HV
• Short-circuit backup protection and overcurrent protection is provided by the building
installation.
• The electrical outlets supplying power to the equipment should be installed near the
equipment and easily accessible.
• Do not connect the PDU to an ungrounded outlet or to extension cords or adapters
that eliminate the connection to ground.
• The plug on the power supply cord is intended to serve as the disconnect device.
Be sure that the socket-outlet is installed near the equipment and is made easily
accessible.
• Never attempt to install electrical equipment during a thunderstorm.
• The power requirement for each piece of equipment connected to the PDU must not
exceed the individual outlet's load rating.
• The total power requirement for equipment connected to the PDU must not exceed the
maximum load rating for the PDU.
• Do not attempt to modify the PDU, input plugs or power cables.
• Do not drill into or attempt to open any part of the PDU housing. There are no user-
serviceable parts inside.
• Do not attempt to use the PDU if any part of it becomes damaged.
18-11-318-933312.indb 2
Series Number
AGIB6672
AGPD6673
AGPD6674
AGPD6675
2
Overcurrent Protection
30A
30A
20A
30A
3/20/2019 1:22:51 PM