Purge The Air From The System - mabe MMT09CABWCCCHI8 Manual Instructivo

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

purge the air from the system

The air that contains moisture and remains in the refrigeration cycle
may cause a malfunction on the compressor. After connecting the
indoor and outdoor units, release air and moisture from the refrig-
erant using a vacuum pump, as described below.
Note: To protect the environment, be sure not to discharge the re-
frigerant directly into the air.
1. Unscrew and remove caps from the 2 and 3-way valves.
2. Unscrew and remove cap from the service valve.
3. Connect vacuum pump flexible hose to the service valve.
4. Run vacuum pump for 10 to 15 minutes until reaching a vacuum
of 10 mmHg absolute.
5. With vacuum pump still running, close the low pressure knob on
vacuum pump manifold, then stop the vacuum pump.
6. Open 2-way valve 1/4 turn, then close it after 10 seconds. Check
tightness of all joints using liquid soap or an electronic leak detec-
tor.
7. Turn 2 and 3-way valves stems to fully close both valves. Discon-
nect the flexible vacuum pump hose.
8. Replace and tighten all valve caps.
wifi ready (no included)
To enable the WiFi function it will be necessary to acquire and
connect the USB module to the device. Call your authorized service
provider.
91

Hide quick links:

Publicidad

Capítulos

Tabla de contenido
loading

Tabla de contenido