Technical Data; Model Identification; Commissioning The Device; Operations Prior To Installation - Madas EVQ-1 Manual Del Usuario

Electroválvula automática normalmente cerrada para gas
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

2.0 - TECHNICAL DATA

• Use
• Ambient temperature (TS)
• Supply voltages (see table 2)
• Supply voltage tolerance
• Electric wiring
• No. cycles/hour**
• Absorbed power
• Maximum operating pressure
DN 32 - DN 40 - DN 50
DN 65 - DN 80 - DN 100 - DN 125 - DN 150
• Opening time adjustment
• Closing time
• Protection rating
• Class
• Mechanical resistance
• Rp Threaded connections
• PN 16 Flanged connections that can couple with flanges : (DN 32 - DN 40 - DN 50 - DN 65 - DN 80 - DN 100 - DN 125 - DN 150)
• NPT threaded or ANSI 150 flanged connections : on request
• In compliance with (see also table on page 22) : Regulation (EU) 2016/426 (Appliances burning gaseous fuels)
* Only single-phase, the device does not work if powered with three-phase voltage
** For cycles/hours with ON/OFF times different from those indicated, contact our technical office

2.1 - MODEL IDENTIFICATION

EVQ-1 : Adjustable slow opening + adjustable fast stroke
EVR-1 : Adjustable slow opening + flow rate adjustment
EVS-1 : Adjustable slow opening + adjustable fast stroke + flow rate adjustment
EVT-1 : Adjustable slow opening
EVQ-3 : Adjustable slow opening + adjustable fast stroke
EVR-3 : Adjustable slow opening + flow rate adjustment
EVS-3 : Adjustable slow opening + adjustable fast stroke + flow rate adjustment
EVT-3 : Adjustable slow opening
EVQ-6 : Adjustable slow opening + adjustable fast stroke
EVR-6 : Adjustable slow opening + flow rate adjustment
EVS-6 : Adjustable slow opening + adjustable fast stroke + flow rate adjustment
EVT-6 : Adjustable slow opening
2.2 - SIL LEVEL
For models in compliance with Regulation (EU) 2016/426 (see table in 9.0), the SIL level of the stand-alone solenoid valve
is SIL 2; when two solenoids are installed in series and the relative leak test (Valve Proving System), certified according to
EN 1643, the achieved level is SIL 3, as set forth in EN 676:2008. The solenoid valve has PL d level. For further data refer
to the SIL LEVEL table (table 2).

3.0 - COMMISSIONING THE DEVICE

3.1 - OPERATIONS PRIOR TO INSTALLATION

• It is necessary to close the gas upstream of the valve prior to installation;
• Make sure that the line pressure DOES NOT EXCEED the maximum pressure declared on the product label;
• Any protective caps (if any) must be removed prior to installation;
• Valve pipes and insides must be clear of any foreign bodies;
If the device is threaded:
• make sure that the pipe thread is not too long, to prevent damaging the body of the device when screwing it on;
EV(Q-R-S-T)-1-3-6
: non-aggressive gases of the three families (dry gases)
: -20 ÷ +60 °C
: 24 Vdc - 24 V/50 Hz - 110 V/50-60 Hz - 230 V/50-60 Hz*
: -15% ... +10%
: cable gland PG 11
:
90 (ON time 10s - OFF time 30s)
~
: see table 2
: 3 bar or 6 bar (see product label)
: 500 mbar,1 bar, 3 bar or 6 bar (see product label)
: between 0.5 and 30 s ± 20% (ta= 25 °C - V=Vn)
: < 1 s
: IP65
: A
: Group 2
: (DN 32 - DN 40 - DN 50) according to EN 10226
ISO 7005 / EN 1092-1
PED Directive 2014/68/EU (versions with P.max = 1-3-6 bar)
EMCDirective 2014/30/EU - LVD Directive 2014/35/EU
RoHS II Directive 2011/65/EU
14
Madas Technical Manual - 1|1.5d - REV. 1 of 10
P.max = 0.5 or 1 bar
P.max = 0.5 or 1 bar
P.max = 0.5 or 1 bar
P.max = 0.5 or 1 bar
P.max = 3 bar
P.max = 3 bar
P.max = 3 bar
P.max = 3 bar
P.max = 6 bar
P.max = 6 bar
P.max = 6 bar
P.max = 6 bar
Sep 2020
th

Publicidad

Tabla de contenido
loading

Tabla de contenido