F
E
14/16kW
E
Model
80
A
910
B
982
C
390
D
345
E
120
F
663
G
712
H
375
I
426
Drawing No.
Fig.3-1,Fig.3-2
Fig.3-4
A
B
Fig.3-5
F
Fig.3-6
Table 3-1(unit:mm)
100/120
140/160
950
1040
/
1053
406
452
360
410
175
191
590
656
840
865
390
463
440
523
Fig.3-3,Fig.3-4
Fig.3-5,Fig.3-6
Single unit installation
(Wall or obstacle)
Air inlet surface
> 300
Air inlet
surface
> 2000
Parallel connect the two units or above
> 300
> 600
> 2000
Parallel connect the front with rear sides
> 2000
> 500
3.3 Moving and installation
Since the gravity center of the unit is not at its physical center,
so please be careful when lifting it with a sling.
Never hold the inlet of the outdoor unit to prevent it from
deforming.
Do not touch the fan with hands or other objects.
Do not lean it more than 45°, and do not lay it sidelong.
Make concrete foundation according to the sepecifications of
the outdoor units.(refer to Fig.3-7)
Fasten the feet of this unit with bolts firmly to prevent it from
collapsing in case of earthquake or strong wind.
(refer to Fig.3-7)
> 600
13
> 300
Maintenance cable
and pipeline surface
> 600
Air outlet surface
> 3000
> 3000
Fixed with a bolt
Fig.3-4
Fig.3-5
> 300
Fig.3-6
Fig.3-7