INTRODUCTION
EN
This instruction sheet provides you with the information required to safely own
and operate your Little Giant pump. Retain these instructions for future reference.
The Little Giant pump you have purchased is of the highest quality workmanship
and material, and has been engineered to give you long and reliable service.
Little Giant pumps are carefully tested, inspected, and packaged to ensure safe
delivery and operation. Please examine your pump carefully to ensure that no
damage occurred during shipment. If damage has occurred, please contact the
place of purchase. They will assist you in replacement or repair, if required.
READ THESE INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING TO
INSTALL, OPERATE, OR SERVICE YOUR LITTLE GIANT PUMP. KNOW
THE PUMP'S APPLICATION, LIMITATIONS, AND POTENTIAL HAZARDS.
PROTECT YOURSELF AND OTHERS BY OBSERVING ALL SAFETY
INFORMATION. FAILURE TO COMPLY WITH THESE INSTRUCTIONS
COULD RESULT IN PERSONAL INJURY AND/OR PROPERTY DAMAGE!
DESCRIPTION
The Little Giant VCMX-20 automatically removes condensation from air
conditioners and high-efficiency gas furnaces. A float/switch mechanism turns
the pump on when approximately 1.6" of water collects in its tank, and turns the
pump off when the tank drains to approximately 1.2". A safety overflow switch
activates when water in the tank rises to approximately 2.2", turning off the
thermostat or turning on an alarm (depending upon wiring configuration).
SAFETY GUIDELINES
Do not use to pump flammable or explosive fluids such as gasoline, fuel oil,
kerosene, etc. Do not use in explosive atmospheres. Pump should be used
with liquids compatible with pump component materials.
Do not handle pump with wet hands or when standing on a wet or damp
surface, or in water. This pump is supplied with a grounding conductor
and/or grounding type attachment plug. To reduce the risk of electrical
shock, be certain that it is connected to a properly grounded grounding
type receptacle.
In any installations where property damage and/or personal injury might
result from an inoperative or leaking pump due to power outages,
discharge line blockage, or any other reason, a backup system(s) and/or
alarm should be used.
Support pump and piping when assembling and when installed.
Failure to do so may cause piping to break, pump to fail, motor
bearing failures, etc.
Ensure bracket is level
S'assurer que support de fixation
est de niveau
Asegúrese de que el soporte de
Mounting bracket
Support de montage
montaje esté a nivel
Soporte de montaje
Bracket screws
Vis du support
Tornillos del soporte
STANDARD PUMP • POMPE STANDARD • BOMBA ESTÁNDAR
Anti-sweat sleeve
Gaine anticondensat
Camisa anticondens
Mounting bracket
Support de montage
Soporte de montaje
ANTI-SWEAT PUMP • POMPE ANTICONDENSATION
• BOMBA ANTICONDENSACIÓN
Figure • Figure • Figura 1
VCMX-20
CONDENSATE PUMP •
POMPE À CONDENSATS
• BOMBA DE CONDEN-
SACIÓN
Wall • Paroi • Pared
Mounting bracket
Support de montage
Soporte de montaje
Wall • Paroi • Pared
Bracket screws
Vis du support
Tornillos del soporte
INSTALLATION
CAUTION: Do not install this pump where it can be splashed or sprayed.
CAUTION: Do not use this pump inside air plenums.
1. Carefully unpack the pump. Using the enclosed mounting bracket, mount the
pump either on the side of the air conditioner/furnace or on a nearby wall.
(See Figures 10 and 11 for pump dimensions.) The tank has a mounting slot
on each side so it can be positioned either way (Figure 1). Ensure that the
pump is level and the inlet is below the coil drain. Conduit fittings are not
compatible with the plastic pump housing.
Pumps with an anti-sweat sleeve use a different mounting bracket, but the
mounting location holes are the same and the brackets are interchangeable.
If mounting the pump on a flat surface, install the enclosed 4 rubber feet onto
the bottom of the tank.
2. Fully insert the enclosed check valve into the discharge line, ensuring that
the O-ring and discharge line are free of debris (Figure 2).
Figure • Figure • Figura 2
3. Insert the check valve into the pump discharge hole and twist it by hand 1/4
turn (Figure 3).
Figure • Figure • Figura 3
4. Check to ensure that the valve is securely locked into position (Figure 4).
Figure • Figure • Figura 4
ELECTRICAL CONNECTIONS
WARNING: All wiring must be performed by a qualified service technician.
Check local electrical and building codes before installation. The installation
must be in accordance with their regulations as well as the most recent National
Electrical Code (NEC).
1. Shut off electrical power at fuse box before making any connections. All
wiring must comply with local codes.
2. Line voltage: Connect power cord to line voltage specified on motor and
nameplate. Power cord must be connected to a constant source of power
(not a fan or other device that runs intermittently). If power cord does not
have a plug, wiring is as follows: green (or green/yellow) is ground, black (or
brown) is line, and white (or blue) is neutral.
1

Publicidad

Tabla de contenido
loading

Resumen de contenidos para Little Giant VCMX-20

  • Página 1 Little Giant pump. Retain these instructions for future reference. Pumps with an anti-sweat sleeve use a different mounting bracket, but the The Little Giant pump you have purchased is of the highest quality workmanship mounting location holes are the same and the brackets are interchangeable.
  • Página 2 Slope down from highest point Le produit Little Giant que vous avez acheté a été soigneusement fabriqué avec Inclinaison à partir du point le plus haut des matériaux de la plus haute qualité et a été conçu pour durer longtemps Coloque en declive, desde el punto más alto...
  • Página 3: Connexions Electriques

    1. Couper la source d’alimentation électrique au niveau de la boîte à fusibles El producto Little Giant que ha adquirido se fabrica utilizando mano de obra y avant d’effectuer quelque connexion que ce soit. L’intégralité du câblage materiales de la más alta calidad y ha sido diseñado para prestarle un servicio doit respecter les codes locaux.
  • Página 4: Descripción

    DESCRIPCIÓN de que quede posicionado entre dos canales en la tapa del motor (figura 5). La bomba Little Giant VCMX-20 automáticamente elimina la condensación de Para la conexión de los circuitos NC vea la figura 5. los aires acondicionados y las calderas a gas de alta eficiencia. El mecanismo flotador/interruptor enciende la bomba cuando se recolecta aproximadamente 4.
  • Página 5 Figure • Figure • Figura 9 DESCRIPTION • DESCRIPTION • DESCRIPCIÓN Tank, black, polypropylene • Réservoir, noir, polypropylène • Tanque negro de polipropileno 154390 Feet, rubber (4 pack) • Pied, caoutchouc (paquet de 4) • Patas de caucho (paquete de 4) 925047 Cover, motor, blue, ABS •...
  • Página 6 Models with vibration-dampening feet and standard bracket Modèles avec pieds antivibrations et support standard Modelos con patas que amortiguan las vibraciones y soporte estándar Figure • Figure • Figura 10 Models with anti-sweat sleeve and bracket Modèles avec gaine anticondensation et support Modelos con camisa anticondensación y soporte estándar Figure •...
  • Página 7: Garantie Limitée

    Any product that should fail for either of the above two reasons and is still within the D’APTITUDE PARTICULIÈRE, POUVANT S’APPLIQUER À UNE POMPE warranty period will be repaired or replaced at the option of Little Giant as the sole LITTLE GIANT. DE PLUS, ELLE NE S’APPLIQUE QUE DURANT LA remedy of buyer.
  • Página 8 ..... . . 1.888.572.9933 Para la ayuda técnica, por favor póngase en contacto ..1.888.956.0000 www.LittleGiantPump.com CustomerService-WTS@fele.com Form 998632 - 08/2008 ©2008 Franklin Electric Co., Inc. Little Giant® is a registered trademark of Franklin Electric Co., Inc.

Tabla de contenido