S&P COR-1000 NW9 Manual De Instalación. Instrucciones De Uso página 7

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 1
ENGLISH
The models in this range offer the possibility of
working as hot/cold air curtains.
We advise you to check that the unit is in
perfect condition when unpacking it, as any
manufacturing or quality defect is covered by
the S&P guarantee.
IMPORTANT: SAFETY GUIDELINES
The appliance must not be right above or
below a socket.
Do not cover the unit with clothes or objects
that may obstruct the airflow and cause
overheating.
While in operation, the connection cable must
not be in front of the air outlet.
If it is installed in the bathroom, it must be
placed so that the switches or other control
devices cannot be touched by anyone in the
bathtub or shower.
There must not be any inflammable objects at
less than 50 cm from the unit (such as window
curtains, etc.).
Keep the inlet and outlet grilles clean. When
cleaning them, disconnect the unit from the
mains supply.
Do not manipulate the unit with wet hands.
The installation work must be carried out by an
electrician.
IMPORTANT: THIS APPLIANCE MUST BE
.
EARTHED
The means of disconnection from the mains
supply must have an opening distance of at
least 3 mm in all poles.
To operate the unit as an Air Curtain, the
maximum distance to the floor must not be
greater than 3 metres.
The minimum distance between the Air
Curtain and the floor must be 1,8 metres.
INSTALLATION
The unit must be fixed to a convenient
surface, and the minimum distances shown
on Fig. 1 must be kept.
To install the unit, proceed as follows:
If the spiral nuts already placed in the device
are used, there must be marked the centers of
the screws (M-8) according to the table of
Fig.2 (a) and Fig.2 (b). If the hanging fixation is
used, the centers must be marked according
to the table of Fig.3 (a) and Fig.3 (b) and place
the screws (D) and the set squares (E). Then
hang the device and to fix on the lowest part
with the screw (G).
To access the connection cards you must
open the front grille.
The maximum working pressure of the water
radiator must not exceed 4 Kg/cm .
The maximum temperature of the hot water
must not exceed 95ºC.
The water coil must not operate at
temperatures of less than 5ºC. When there is a
risk of the temperature dropping below this
limit antifreeze liquid must be used or the
installation must be emptied.
The water pump must be connected to the coil
via the 1/2" gas thread inlets fitted for this
purpose.
ELECTRICAL CONNECTION
They are installed appliances. When
connecting them to the mains, the standards
and regulations in force in your country must
be strictly adhered to.
Within the installation an electrical isolation
switch must be present, to enable the installer
to cut all supply lines.
Connect the unit to the mains supply, checking
that the voltage and frequency are the same
as those indicated on the electrical rating
plate.
Use the cables with the number of wires and
sections as indicated on the wiring diagram for
every model.
Fix the cables with the clamp provided.
OPERATION
REMOTE CONTROL CONNECTION. (This
control is incorporated in the packaging of
each air curtain).
CURTAIN
MODEL
COR-1000 NW9
COR-1500 NW15
7
2
Fig. 4
REMOTE CONTROL
MODEL
CR-NW
CR-NW

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Cor-1500 nw15

Tabla de contenido