RUN indicator: flashes
ALARM indicator: off
Setting/monitor indicators: FREF, FOUT or IOUT is lit.
Data display: displays the corresponding data for the indicator that is lit.
When fault has occurred, the details of the fault will be displayed. In that case, refer to user's
manual and take necessary action.
Step 3 – Initializing parameters
To initialize the drive parameters to factory defaults, set parameter n01 = 8. This will set the J7 to
accept start/stop commands in what in termed "2-wire control", i.e. 1 wire for a motor forward/stop
command, and 1 wire for a motor reverse/stop command.
Key
Indicator
Sequence
In approximately
1s.
Step 4 – Set the motor rated current
This parameter is used for the electronic thermal function for motor overload detection (OL1). By cor-
rectly setting this, the J7 will protect an overloaded motor from burning out.
Read the rated current (in amps) on the motor nameplate, and enter this into parameter n32. The
example to the below shows entering a value of 1.8Amps.
Key
Indicator
Sequence
In approximately1s.
Display
Explanation
example
Power On
Press the Mode Key repeatedly until the PRGM indicator is lit.
Press the Enter Key. The data of n01 will be displayed.
Use the Increment or Decrement Key to set n01 to 8. The display will
flash.
Press the Enter Key so that the set value will be entered and the data
display will be lit.
The parameter number will be displayed.
Display
Explanation
example
Displays the parameter number
Use the Increment or Decrement Key until n32 is displayed.
Press the Enter Key. The data of n32 will be displayed.
Use the Increment or Decrement Key to set the rated motor current. The
display will flash.
Press the Enter Key so that the set value will be entered and the data
display will be lit.
The parameter number will be displayed.