8.4) PARAMETERS, LOGICS AND SPECIAL FUNCTIONS
The following tables describe the functions available on the control unit.
MENU
Automatic closing time. Enabled only with logic "TCA"=ON.
TCA
At the end of the set time, the control unit commands a closing maneuver .
tped
The passage left open by the gate leaf during the partial opening (pedestrian) is adjusted.
fsto
The opening speed is adjusted.
fstc
The closing speed is adjusted.
sldo
Adjusts the slowdown speed of sliding door during the opening phase* (Fig.10 -slow Open).
sldc
Adjusts the slowdown speed of sliding door during the closing phase * (Fig.11 -slow Close).
Sets the starting point of the slowdown during the opening phase (Fig.10- beginning of the slow
tsmo
Open). The value is expressed in percentage on the entire stroke.
Sets the starting point of the slowdown during the closing phase (Fig.11- beginning of the slow
tsmc
Close). The value is expressed in percentage on the entire stroke.
PMO
Adjusts the motor torque applied to sliding door during the opening phase.*
PMC
Adjusts the motor torque applied to sliding door during the closing phase.*
Adjusts the motor torque applied to sliding door during the slowdown in opening phase * (Fig.9
PSO
- Slow Open).
Adjusts the motor torque applied to sliding door during the slowdown in closing phase * (Fig.10
PSC
- Slow Close).
Activation time of the courtesy light contact. Value expressed in seconds. At the beginning of
tls
each maneuver the contact latches for the set time. See the description of AUX1 parameter.
It selects the operating mode of the AUX 1 output:
0: Open gate indicator light. The light is off when the door is closed, flashes with moving door
and is on with open door. See wire diagram.
1: Second radio channel. The output is controlled by the radio channel of the built-in receiver
aux1
(see RADIO Menu).
2: Service light. The contact closes for the time preset with TLS parameter. The countdown
starts at the inception of operation.
3: Photo-test Used to power the photocell transmitters in TEST mode
See wiring diagram Fig.23.
Same operation features as AUX1 output, but referred to terminals AUX2.
aux2
ATTENTION!: Max AUX2 output voltage is 24Vdc/0,5 A Max. You can directly power 24Vdc
devices, as shown in Fig. 24.
* ATTENTION: A WRONG SETTING OF THESE PARAMETERS CAN BE DANGEROUS.
RESPECT THE REGULATION IN FORCE!
Measure that impact forces comply with the values laid down in regulation en 12445. change, if necessary, the operating parameters and repeat the measurements.
Once you have manually modified the parameters sldo, sldc, pmo, pmc, pso, psc, the controller performs a complete manoeuvre to learn the new
parameters and "PRG" appears on display.
MENU
Enables or disables automatic closing
TCA
On: automatic closing enabled
Off: automatic closing disabled
Enables or disables condominium function.
On: condominium function enabled. The step-by-step impulse or transmitter impulse has no
IbL
effect during the opening phase.
Off: condominium function disabled.
The multi-flat function is enabled or disabled during the TCA counting.
On: the bloc of flat function is enabled. The Step-by-Step signal or the transmitter signal has no
ibca
effect during the TCA counting.
Off: the bloc of flat function is disabled.
The rapid closure is enabled or disabled
On: rapid closure is enabled. When the gate is open or moving, the photocell activation causes
SCL
the automatic closure of the gate after 3 s. It is activated only with TCA:ON
Off: rapid closure is disabled.
Selects the operating mode of the "Step by step button" and of the transmitter.
PP
On: Operation: OPEN > CLOSE > OPEN >
Off: Operation: OPEN > STOP > CLOSE > STOP >
Enables or disables pre-blinking.
PRE
On: Pre-blinking enabled. Blinking is activated 3s before the motor starts.
Off: Pre-blinking disabled.
8.4.1) PARAMETERS (PAR)
FUNCTION
8.4.2) LOGICS (LOG)
FUNZIONE
MEMO
MIN-MAX-(Default)
3-240-(40)
10-99-(50)
50-99-(99)
50-99-(99)
10-50-(25)
10-50-(25)
1-99-(20)
1-99-(20)
1-99-(20)
1-99-(20)
1-99-(20)
1-99-(20)
1-240 (60)
0-3-(1)
0-3-(0)
MEMO
ON-OFF-(Default)
(ON)
(OFF)
(OFF)
(OFF)
(OFF)
(OFF)
EN