Electrical connections
Electrical connections (power supply) must be performed by a qualified electrician in compliance with local stan-
dards (NFC 1500 in France).
- The pump, electronic box and power cable must not be
accessible from the bath during use. Zone 1 under the bath
should only be accessed with a tool.
- The power supply cable must be permanently connected to a
fixed 230V/50 Hz, 16 A+ protective earth supply, as per local
standards. It must be protected by a differential circuit brea-
ker (maximum 30mA) installed outside Zones 0, 1, 2 and 3.
- Use power cable type 60227 IEC 53 or H05VV-F with two
conductors + protective earth supply 1.5mm2 and the IPX5
protection junction box supplied with the bath.
- This junction box should only be installed in Zone 1, under the
bath.
- I f p o w e r c a b l e i s d a m a g e d , i t s h o u l d o n l y b e re p l a c e d b y t h e m a n u f a c t u re r, an after-sales
department or a qualified professional.
- As per local standards (NFC 15100 in France) , an equipotential link made inside bathroom must connect all
conductive parts and components in Zones 1, 2 and 3 (metal bath, metal waste, taps, bath frame).
- Perform equipotential link via terminal marked with an "
Apron/Wall finish
NOTE: After the tiles and seals have dried thoroughly, fill the whirlpool with
water up to the overflow to test for water tightness and proper system ope-
ration. An access panel should be provided for servicing whirlpool compo-
nents. We recommend a removable panel along the full width of the bath for
this purpose.
Cut away outer section of insulating strip.
mastique
Fill the space between the wall finish and the edge of the bath with silicone
silicone
sealant.
The panel should be properly sealed with an anti-fungal bead, but leave
lower edge unsealed to allow ventilation to the system. (In compliance with
faiança
local standards, the access panel should only open with a tool).
cola
Allow the sealant to harden then empty the whirlpool.
silicone
mastic
Tiling
Glue
mastique
silicone
posição
faiança
da banheira
vazia
cola
silicone mastic
Tiling
Position
Glue
of empty
bath
Zone 2
=>2.25 m
Outside Zones
"symbol located on the bath support frame.
posição
da banheira vazia
Position of empty bath
1 5
Outside Zones
Zone 1
Zone 1
Zone 0
Zone 1
Zone 2
Outside Zones
Cimento-cola
Revestimento mural
5 mm
Massa /
silicone
Cola
Régua de suporte em madeira
5 mm
wall
silicone mastic
Wood support block
Zone 2
=>2.25 m
Outside Zones
Posição
da banheira
vazia
Posição
da banheira
cheia
cement glue
wall covering
Position of
empty bath
Position of full bath
ciment colle