Technical Specifications - RS V9031 Hoja De Instrucciones

Kit de control electrónico de fotocélula
Tabla de contenido

Publicidad

General
The RS Photo-cell control kit is designed to automatically switch
lighting (or other) loads ON and OFF depending on the ambient lighting
levels. The unit has factory set lighting levels and is omni-directional
i.e., it does not need north orientation. Additionally it has a built-in time
delay to stop unwanted nuisance switching by car headlights, passing
clouds etc.
The kit comprises of the following:-
1 x Photo-electric cell
1 x Rotaloc socket
1 x Gasket
1 x Dust cap
4 x Posidrive socket fixing screws
1 x Fixing bracket
1 x Rubber grommet
3 x No. 8 x 11⁄4" wood screws
3 x No. 8 wall fixing plugs
Installation
Before installation choose a suitable locating for the controller, avoiding
positions where light from other sources can influence the switching,
also locations which may fall into shadow in the morning and evening
i.e. eaves of a building. As a general rule the controller should also be
mounted in a position that makes it inaccessible to unauthorised
personnel.
To install the Photo-cell (refer to Fig 2).
1. Drill mounting holes for the fixing bracket, using the bracket as a
template. Fix securely in position using a No. 8 masonry drill and the
wall plugs and screws supplied.
2. Puncture the rubber grommet located at the base of the mounting
bracket and install appropriate cable or alternatively remove
grommet and connect 20mm conduit.
The controller may be used to directly switch lighting loads up to its
maximum rating (Technical Specification) or alternatively it may be
used in conjunction with a contactor to supply a multi-load
installation (refer to Figs 2 and 3 for typical wiring diagrams).
3. Before connecting cable to socket, ensure that the neoprene gasket
is located between the bracket and the socket.
4. Connect cable as per fig 4.
Li = Line=Live (phase) supply
N = Neutral=Neutral
LO = Load=Outgoing switched live
Neutral connection can be used as looped connection to neutral
terminal on load if required (Figs 2 and 3).
5. Fix socket to bracket using the 4 posidrive screws provided.
6. Plug the Photo-cell unit into the socket by pushing down firmly and
then twisting clockwise to its full extent.
The Photo-cell unit will only fit the socket in one position. Ensure
that the large lug on the cell locates in the large slot of the socket.
7. Once the kit is fully assembled the unit is now ready for connection
to the supply. Check the connections on the load being supplied
before switching on.
When supply is first switched on, unit will be alive and the load will
be switched on. After 35 seconds the unit should switch off. To test
the unit cover the Photo-cell completely, the load will switch on.
Important
Supply to the Photo-cell must be maintained at all times. The supply to
the Li terminal will still be alive when the load is switched off.
Testing
RS Stock No.
Insulation testing by a suitable instrument can be carried out on circuits
including Photo-cells, but not continuity tests as the high voltage used
571-439
may seriously damage the cell.

Technical Specifications

Type of control:__________________________________Electronic
Supply voltage: ____________________220V - 270V a.c. 50/60Hz
Rating: ______________Maximum lamp load 3 x 400W HPS (SON)
Switch on level: ____________________________________70 lux
Switch off level: ____________________________________35 lux
Operation: ______________________________________All night
RS Components shall not be liable for any liability or loss of any nature (howsoever
caused and whether or not due to RS Components'negligence) which may result
from the use of any information provided in RS technical literature.
Allgemein
Die RS Fotozellensteuerung wurde entwickelt, um automatisch
Lichtschaltkreise (oder andere) in Abhängigkeit von der Stärke des
Umgebungslichts ein- und auszuschalten. Diese Einheit ist ungerichtet
(eine
Lichtstärkepegel sind werkseitig eingestellt. Sie verfügt außerdem über
eine eingebaute Zeitverzögerung, um Fehlschaltungen durch die
Scheinwerfer eines Autos, durch vorüberziehende Wolken usw. zu
vermeiden.
Zum Lieferumfang gehören:
1 Fotozelle
1 Rotaloc-Buchse
1 Dichtung
1 Staubkappe
4 Schrauben zur Befestigung der Posidrive-Buchse
1 Halterung
1 Durchführungstülle aus Gummi
3 Holzschrauben 8 x 11⁄4"
3 Dübel Nr. 8
Montage
Wählen Sie vor der Montage den geeigneten Platz für die Steuerung
aus. Vermeiden Sie Stellen, an denen einfallendes Licht von anderen
Quellen das einwandfreie Schalten beeinflußen kann und solche
Stellen, die morgens und abends im Schatten liegen, d.h. Vordächer.
Die Steuerung sollte im allgemeinen so montiert sein, daß sie für
unbefugte Personen nicht zugänglich ist.
Montage der Fotozelle (siehe Abb. 2)
1. Bohren Sie die Löcher für die Halterung. Benutzen Sie die
Halterung als Schablone. Benutzen Sie einen Maurerbohrer Nr. 8,
setzen Sie die Dübel ein, und befestigen Sie die mitgelieferten
Schrauben.
2. Durchstechen Sie die Gummitülle im Sockel der Halterung, und
ziehen Sie das entsprechende Kabel ein. Sie können die Tülle auch
entfernen und ein 20mm Kabel anschließen.
Mit dem Steuergerät können Sie Lichtlasten bis zu ihrer maximalen
Leistung direkt schalten (siehe "Technische Daten"). Sie können es
auch
Mehrlastanschluß benutzen (siehe die Abbildungen 2 und 3 der
typischen Verdrahtungspläne).
3. Bevor Sie das Kabel an die Buchse anschließen, sollten Sie
sicherstellen, daß die Neoprendichtung richtig zwischen Halterung
und Buchse sitzt.
Nordausrichtung
ist nicht erforderlich).
in
Verbindung
mit
einem
V9031
Maximum tungsten load 2000W
RS Best-Nr.
571-439
Die
einzelnen
Schaltschütz
für
einen
3

Publicidad

Tabla de contenido
loading

Tabla de contenido