NORMAL OPERATION / FLAME DETECTION TIME
The control box has a further function to guarantee the correct burner operation (signal: GREEN LED permanently on).
To use this function, wait at least ten seconds from the burner ignition and then press the control box button for a minimum of 3 seconds.
After releasing the button, the GREEN LED starts flashing as shown in the figure below.
GREEN LED on
wait at least 10s
The pulses of the LED constitute a signal spaced by approximately 3 seconds.
The number of pulses will measure the probe DETECTION TIME since the opening of gas valves, according to the following table:
SIGNAL
1 blink
2 blinks
6 blinks
ACCESSORIES (optional):
•
RADIO DISTURBANCE PROTECTION KIT: code 3010386
If the burner is installed in places particularly subject to radio disturbance (emission of signals exceeding 10 V/m) owing to the presence of an
INVERTER, or in applications where the length of the thermostat connections exceeds 20 metres, a protection kit is available as an interface
between the control box and the burner.
•
KIT LONG HEAD: code 3010443
•
KIT FOR LPG OPERATION: code 3010166
The kit allows the RS 190 burners to operate on LPG
BURNER
Output
•
VIBRATION REDUCTION KIT: code 3010375
BURNER
Output
•
KIT INTERFACE ADAPTER RMG TO PC: code 3002719
•
GAS TRAIN ACCORDING TO REGULATION EN 676 (with valves, pressure governor and filter): see page 8.
Important
The installer is responsible for the addition of any safety
device not forseen in the present manual.
Press button
for > 3s
FLAME DETECTION TIME
0.4s
0.8s
2.8s
RS 190
kW
465 ÷ 2290
RS 190
kW
470 ÷ 2147
20
Interval
signal
3s
This is updated in every burner start-up.
Once read, the burner repeats the start-up cycle by briefly
pressing the control box button.
WARNING
If the result is > 2s, ignition will be retarded.
Check the adjustment of the hydraulic brake of the gas
valve, the air damper and the combustion head adjustment.
signal