4. Call the "4. INITA" parameter. To do this, briefly press the
5. Start the initialization process. To do this, press the
following:
The positioner runs through five initialization steps during the automatic initialization process. Displays for the
initialization steps from "RUN1" to "RUN5" are shown in the lower line on the digital display. The initialization process
depends on the actuator used, and takes up to 15 minutes.
6. The following display indicates that the automatic initialization is complete. The total angle of rotation of the actuator is
shown on the upper line on the digital display:
Aborting the automatic initialization process
1. Press the
button. The digital display shows the following:
The positioner is in the "Configuration" mode.
2. Exit the "Configuration" mode. To do this, press the
The software status is displayed.
After releasing the

Manual initialization of part-turn actuators

See detailed operating instructions for information on manual initialization of part-turn actuators.
34
button, the positioner is in "P manual mode". The part-turn actuator is not initialized.
button. The digital display shows the following:
button for at least 5 seconds until the digital display shows the
button for at least 5 seconds.
SIPART PS2 (6DR5...)
A5E03436620-01, 03/2011