Descargar Imprimir esta página

EAS ELECTRIC EDM Serie Manual De Usuario E Instalacion página 106

Publicidad

Idiomas disponibles

Idiomas disponibles

A
r E
v
i
a
c
a
i º
u
t
L_
_
_
_
_
_
_
_
_
_
Safety Precautions
OcAUTION
• Use a vacuum pump with a gauge reading
lower than -0.lMPa and an air discharge
capacity above 40L / min.
• The outdoor unit does not need vacuuming.,
DO NOT open the outdoor unit's gas and
liquid stop valves.
• Ensure that the Compound Meter reads
-0.lMPa or below after 2 hours. lf after
three hours the gauge reading is still above
-0.lMPa, check if there is a gas leak or
water inside the pipe. lf there is no leak,
perform another evacuation for 1 or 2 hours.
, DO NOT use refrigerant gas to evacuate the
system.
Evacuation lnstructions
Before using a manifold gauge and a vacuum
pump, read their operation manuais to make
sure you know how to use them properly.
Manifold Gauge
Compound gauge
-76cmHg
Low pressure valve
Fig. 9.1
1. Connect the manifold gauge's charge hose to
the service port on the outdoor unit's low­
pressure valve.
2. Connect the manifold gauge's charge hose
from the to the vacuum pump.
3. O pen the Low-Pressureside of the manifold
gauge. Keep the High-Pressure side closed.
"
______________ _
_
Pressure gauge
High pressure valve
4. Turn on the vacuum pump to evacuate the
system.
5. Run the vacuum for at least 15 minutes, or
until the Compound Meter reads -76cmHG
(-lxlOSPa).
6. Close the manifold gauge's Low-Pressure valve
and turn off the vacuum pump.
7. Wait for 5 minutes, then check that there has
been no change in system pressure.
NOTE: lf there is no change in system pressure,
unscrew the cap from the packed valve (high
pressure valve). lf there is a change in system
pressure, there may be a gas leak.
8. lnsert hexagonal wrench into the packed valve
(high pressure valve) and open the valve by
turning the wrench in a 1 / 4 counterclockwise
turn. Listen for gas to exit the system, then
dose the valve after 5 seconds.
Valve body
Valve stem
9. Watch the Pressure Gauge for one minute to
make sure that there is no change in pressure. l t
should read slightly higher than the atmospheric
pressure.
10. Remove the charge hose from the service port.
11. Using hexagonal wrench, fully open both the
high pressure and low-pressure valves.
OPEN VALVE STEMS GENTL Y
When opening valve stems, turn the hexagonal
wrench until it hits against the stopper. DO NOT
try to force the valve to o pen further.
12. Tighten valve caps by hand, then tighten it
using the proper tool.
26
9
_____;:i ___
Fig. 9.2
V.2
4

Publicidad

loading