OPERATION
• Open by pressing the control knob.
• Select temperature by turning the control knob.
• Timed automatic shut-off after ~7 seconds for basins (+/- 3 seconds according to the European
standard EN-NF 816) and ~30 seconds for showers (+5/-10 at 3 bar according to the European
standard EN-NF 816).
• The products have been designed to withstand both thermal and chemical shocks in line
with current regulations.
• Recommended pressure: 1 - 5 bar.
INSTALLATION
• Do not remove the non-return valves built into the water inlets (essential).
• Fit the connection filters, in the same way as indicated in the instructional images.
Their function is to protect the non-return valves and keep them in place.
THE INSTALLER MUST ENSURE:
• THE SEAL AROUND THE RECESSING HOUSING IS WATERPROOF TO PREVENT ANY INGRESS
OF WATER;
• ANY WATER ACCIDENTALLY ENTERING THE RECESSING HOUSING (E.G. CONDENSATION,
RUN OFF, LEAKS, ETC.) HAS AN EXTERNAL DRAINAGE POINT TO PREVENT ANY STAGNATION;
• THE INTEGRITY OF THE SEALS BETWEEN THE STAINLESS STEEL WALL PLATE AND THE WALL
OR THE WALL PLATE AND THE MIXER AT LEAST ONCE A YEAR, AND MAKE GOOD IF NECESSARY.
If this advice is not followed, water may leak into the wall.
DELABIE cannot be held responsible for any ingress.
FOR FURTHER INFORMATION PLEASE CALL DELABIE TECHNICAL SUPPORT
UK: 01491 821821. ALL OTHER MARKETS: +33 (0)3 22 60 22 74.
FLOW RATE ADJUSTMENT (Fig. 1.I or 2.D or 3.G or 4.H or 5.G)
• The flow rate is pre-set at the factory at 3 lpm at 3 bar pressure for basins, it can be adjusted.
• Shower kits are equipped with ROUND or TONIC JET shower head and the shower panels are set at
6 lpm at 3 bar.
• The shower mixers are pre-set at 12 lpm at 3 bar.
REMEMBER
• Our mixers must be installed by professional installers in accordance with current regulations
and recommendations in your country, and the specifications of the fluid engineer.
• Sizing the pipes correctly will avoid problems of flow rate, pressure loss and water hammer
(see calculation table in our brochure and online at www.delabie.com).
• Protect the installation with filters, water hammer absorbers and pressure reducers to reduce
the frequency of maintenance (recommended pressure from 1 to 5 bar maximum).
• Install stopcocks close to the mixer to facilitate maintenance.
• The pipework, filters, non-return valves, stopcocks, bib taps, cartridge and all sanitary fittings
should be checked at least once a year, and more frequently if necessary.