Solar Charge Controller CML05-2, CML08-2, CML10-2, CML15-2, CML20
User Manual English, Page 2
Low Voltage Disconnect Function (LVD)
The controller has 2 different modes to protect the battery from being deeply
discharged:
1. State of charge controlled: Disconnect at 11.4 V (at nominal load current) up to
11.9 V (at no load current). Normal operation mode for good battery protection.
2. Voltage controlled: Disconnect at 11.0 V fixed setting. Appropriate if bypass loads
draw current directly from the battery.
The controller is preset to Mode 1 from the factory. Changing the mode setting is
described below.
In case of doubts which mode to choose, consult your dealer because this has to be
evaluated depending on the battery used.
Settings
The controller can be configured for special operation. For this purpose, open the
cover of the controller by removing the screws on the back side.
WARNING: The controller should not be opened while connected and in opera-
tion!
When the controller is opened, there are 3 jumpers on the electronic board:
2
3
1
With these jumpers, the following settings can be configured:
Jumper
GEL (1)
LVD (2)
Function
Battery type
Function of low voltage
disconnect
Setting jumper
Liquid
State of charge con-
open
trolled
electrolyte
Setting jumper
GEL (VRLA
Voltage controlled
closed
battery)
Factory setting
Jumper open
Jumper open state-of-
(liquid electro-
charge controlled
lyte)
After completing the setting, replace the cover and tighten it with the screws.
Safety Features
The controller is protected against wrong installation or use:
At the solar termi-
nal
Battery connected
Unrestricted
with correct polarity
Battery connected
Unrestricted
with wrong polarity
Yes, not at 24V
Reverse polarity
system voltage.
Short circuit
Unrestricted
Overcurrent
No protection
Thermal overload
No protection
No connection
Unrestricted
Reverse Current
Unrestricted
Overvoltage
Varistor 56 V, 2,3 J
Undervoltage
Normal operation
WARNING: The combination of different error conditions may cause damage to
the controller. Always remove the error before you continue connecting the
controller!
For changing, put the jumper either on
both contact pins or only on one
contact pin:
Closed jumper
Open
jumper
BUZ (3)
Acoustic alarm signal
Alarm off
Alarm on
Jumper closed
Alarm on
At the battery
At the load terminal
terminal
Normal operation
Unrestricted
Unrestricted. Acous-
Unrestricted
tic Warning
Yes, if only the
Load output is
battery is connected.
protected. Loads
Acoustic Warning
might be damaged.
Unrestricted.
CAUTION: Battery
Unrestricted
must be protected
by fuse.
Controller switches
-----------------------
off load terminal.
Controller switches
-----------------------
off load terminal.
Unrestricted
Unrestricted
-----------------------
-----------------------
Controller switches
Max. 40 V
off load terminal.
Controller switches
Controller switches
off load terminal.
off load terminal.
Error Description
Error
Display
Reason
Battery is low
Overcurrent/ Short
circuit of loads
Loads are not
supplied
Battery voltage too
high (>15.5 / 31.0 V)
Battery wires or
battery fuse damaged,
battery has high
resistance
Battery is empty
Battery has low
after a short
capacity
time
Battery is not
Solar array faulty or
being charged
wrong polarity
during the day
Battery wrong
Battery is connected
polarity
Permanent
with reverse polarity
sound
General Safety and Usage Recommendations
Intended Use
The charge controller is intended exclusively for use in photovoltaic systems with 12 V
or 24 V nominal voltage and in conjunction with vented or sealed (VRLA) lead acid
batteries only.
Safety Recommendations
Batteries store a large amount of energy. Never short circuit a battery under all
circumstances. We recommend connecting a fuse (slow acting type, according to
the nominal controller current) directly to the battery terminal.
Batteries can produce flammable gases. Avoid making sparks, using fire or any naked
flame. Make sure that the battery room is ventilated.
Avoid touching or short circuiting wires or terminals. Be aware that the voltages on
specific terminals or wires can be up to double the battery voltage. Use isolated
tools, stand on dry ground and keep your hands dry.
Keep children away from batteries and the charge controller.
Please observe the safety recommendations of the battery manufacturer. If in
doubt, consult your dealer or installer.
Liability Exclusion
The manufacturer shall not be liable for damages, especially on the battery, caused by
use other than as intended or as mentioned in this manual or if the recommendations
of the battery manufacturer are neglected. The manufacturer shall not be liable if
there has been service or repair carried out by any unauthorized person, unusual use,
wrong installation, or bad system design.

Technical Data

Nominal voltage
12 / 24 V, automatic recognition
Boost voltage
14.5 / 29.0 V (25°C), 2 h
Equalization voltage
14.8 / 29.6 V (25°C), 2 h
Float voltage
13.7 / 27.4 V (25°C)
Low Voltage Disconnect
11.4-11.9 / 22.8-23.8 V controlled by state of charge
Function
11.0 / 22.0 V controlled by voltage
Load reconnect voltage
12.8 / 25.6 V
Temperature compensa-
-4 mV/cell*K
tion
Max. solar panel current
5 / 8 / 10 / 15 / 20 A according to model number @
50°C
Max. load current
5 / 8 / 10 / 15 / 20 A according to model number @
50°C
Dimensions
80 x 100 x 32 mm (w x h x d)
Weight
180 gr
Max. wire size
16 mm² (AWG #6)
Self consumption
4 mA
Ambient temperature
-25 to + 50 °C
range
Case protection
IP 20
Subject to change without notice. Version: CML041214
Made in one of the following countries: Germany – China – Bolivia - India
Phocos AG – Germany
www.phocos.com
Remedy
Load will reconnect as
soon as battery is
recharged.
Switch off all loads.
Remove short circuit.
Controller will switch
on load automatically
after max 1 minute.
Check if other sources
overcharge the battery.
If not, controller is
damaged.
Check battery wires,
fuses and battery.
Change battery
Remove faulty connec-
tion/reverse polarity
Remove reverse
polarity