The above assignment of the functions to the control terminals is the default setting of parame-
ter
Configuration
required. For more configurations, refer to the Operating Instructions.
Digital inputs (X210A.3 ... X210B.2): Low Signal: DC 0 V ... 3 V, High signal: DC 12 V ... 30 V,
Input resistance: 2.3 kΩ, response time: 2 ms (STOA and STOB: 10 ms), PLC compatible
Digital output S1OUT (X210B.3): Low Signal: DC 0 V... 3 V, High Signal: DC 12 V ... 30 V,
Maximum output current: 50 mA, PLC compatible
Multifunction output MFO1 (X210B.4):
Digital output: Low Signal: DC 0 V... 3 V, High Signal: DC 12 V ... 30 V, PLC compatible
GB
Analog output: DC 19 ... 28 V, maximum output current: 50 mA, pulse-width modulated (f
Frequency signal: Output voltage: DC 0 V ... 24 V, maximum output current: 40 mA,
maximum output frequency: 150 kHz
Multifunction input MF1 (X210B.6):
Analog signal: Input voltage: DC 0 ... 10 V (R
Digital signal: Low Signal: DC 0 V ... 3 V, High signal: DC 12 V...30 V, response time: 4 ms, PLC compatible
Conductor cross-section:
The signal terminals are suitable for the following cable sizes:
with ferrule:
without ferrule: 0.14 ... 1.5 mm²
4.2.2 External 24 V power supply X210A.1 & X210A.2
The bidirectional control terminals X210A.1/ X210A.2 can be used as a voltage output or voltage input. By
connecting an external power supply of DC 24 V ±10% to terminals X210A.1/X210A.2, the function of inputs and
outputs as well as the communication can be parameterized and maintained, even when mains voltage is off.
Input voltage range
Rated input current
Peak inrush current
External fuse
Safety
CAUTION
The digital inputs and the DC 24 V terminal of the electronic control equipment can withstand ex-
ternal voltage up to DC 30 V. Avoid higher voltage levels. Higher voltages may destroy the unit.
4.2.3
Control terminal X10
Term.
1 ... 3 Relay output, floating change-over contact, response time approx. 40 ms,
maximum contact load:
make contact: AC 5 A / 240 V, DC 5 A (ohmic) / 24 V
break contact:
64
30 to value 110 or 410. The functions can be assigned to the control terminals as
Technical data of control terminals
0.25 ... 1.0 mm²
Requirements to be met by external power supply
DC 24 V ±10%
Max. 1.1 A
Typically: < 25 A
Via standard fuse elements for rated current, characteristic: slow
Safety extra low voltage (SELV) according to EN 61800-5-1
AC 3 A / 240 V, DC 1 A (ohmic) / 24 V
Quick Start Guide ACU 201, ACU 401, ACU 501, ACU 601
=70 kΩ), Input current: DC 0 ... 20 mA (R
i
Control terminal X10
Description
= 116 Hz),
PWM
=500 Ω),
i