Enter the motor data indicated on the rating plate in the following parameters.
No.
370 Rated Voltage
371 Rated Current
372 Rated Speed
Use the arrow keys to select the required parameter and edit the parameter value.
Use the ENT key to confirm the selected parameter and the parameter values entered.
The rated data of the motor are to be entered according to the specifications on the rating plate
for the motor connection type used (star or delta connection). 
If the data entered devi ate from
the rating plate, the parameters will not be identified correctly. The rated data is to be paramete-
rized as per the motor rating plate. Consider the increased rated current of the connected three-
phase motor when the motor is switched from star to delta.
After input of the machine data, the calculation or examination of the parameters is automati-
cally started. The display changes over to "CALC" for a short time. If the verification of the en-
tered machine data is successful, the guided commissioning procedure continues with the iden-
tification of the parameters (automatic measurement of further machine data).
Note the warnings and error messages displayed during guided commissioning.
To ignore the warning messages, press the ENT key. The guided commissioning is continued. However, it is
recommended that the data be checked and corrected if necessary.
To correct the entered parameter values after the warning or error message, press the ESC key. Use the arrow
keys to switch to the parameter value which is to be corrected.
Further machine data are measured while the drive is at a standstill. These measurements will
be entered automatically in the relevant parameters by the parameter identification feature.
Confirm the display "PAidE" by pressing the ENT key.
Note the warnings or error messages upon completion of the parameter identification.
No signals at digital inputs S1IND (STOA) and S7IND (STOB). If signals were already applied at
the beginning of the guided commissioning, the "StO" message is not displayed.
For release of the output stage, wiring of digital inputs S1IND (STOA) and S7IND (STOB) is requi-
red.
Confirm the final "rEAdY" message by pressing the ENT key.
Canceling the operation with the ESC key or withdrawing the enable signal S1IND (STOA) or
S7IND (STOP) results in an incomplete take-over of the values.
In the case of higher requirements as regards the accuracy of the speed/torque control, you
should carry out the guided commissioning procedure once again under operating conditions be-
cause part of the machine data depends on the operating temperature.
During this procedure, confirm the rated machine values already entered.
Confirm the "End" display by pressing the ENT key.
The guided commissioning of the frequency inverter is terminated via a reset and the initializati-
on of the frequency inverter. The relay output X10 signals a fault.
After successful initialization of the frequency inverter, the factory-set parameter
quency
The drive is accelerated to the set
• Signals at digital inputs S1IND (STOA) and S7IND (STOB) and
• Start clockwise by rising signal edge at S2I ND or
Start anti cl ockw i se by ri si ng si gnal edge at
S3IND
05/16
Description
241 is displayed.
Quick Start Guide ACU 201, ACU 401, ACU 501, ACU 601
No.
374
Rated Cosinus Phi
375
Rated Frequency
376
Rated Mech. Power
418 (default 3.50 Hz) by: