Refrigerant Piping Connection; Note On Pipe Length; Connection Instructions -Refrigerant Piping - Carrier 42QHG009D8S Serie Manual De Instalación

Ocultar thumbs Ver también para 42QHG009D8S Serie:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Refrigerant Piping Connection

When connecting refrigerant piping, do not let substances or gases other than the specified
refrigerant enter the unit. The presence of other gases or substances will lower the unit's
capacity, and can cause abnormally high pressure in the refrigeration cycle. This can cause
explosion and injury.

Note on Pipe Length

The length of refrigerant piping will affect the performance and energy efficiency of the
unit. Nominal efficiency is tested on units with a pipe length of 5 meters (16.5ft) ( In North
America, the standard pipe length is 7.5m (25')). A minimum pipe run of 3 metres is required
to minimise vibration & excessive noise. In special tropical area, for the R290 refrigerant
models, no refrigerant can be added and the maximum length of refrigerant pipe should not
exceed 10 meters (32.8ft).
Refer to the table below for specifications on the maximum length and drop height of piping.
Maximum Length and Drop Height of Refrigerant Piping per Unit Model
Model
R410A,R32 Inverter
Split Air Conditioner
R22 Fixed-speed
Split Air Conditioner
R410A, R32 Fixed-speed
Split Air Conditioner
Connection Instructions – Refrigerant Piping
Step 1: Cut pipes
When preparing refrigerant pipes, take extra
care to cut and flare them properly. This will
ensure efficient operation and minimize the
need for future maintenance.
1. Measure the distance between the indoor
and outdoor units.
2. Using a pipe cutter, cut the pipe a little
longer than the measured distance.
3. Make sure that the pipe is cut at a
perfect 90° angle.
Capacity (BTU/h)
< 15,000
≥ 15,000 and < 24,000
≥ 24,000 and < 36,000
< 18,000
≥ 18,000 and < 21,000
≥ 21,000 and < 35,000
< 18,000
≥ 18,000 and < 36,000
Max. Length (m) Max. Drop Height (m)
25 (82ft)
30 (98.5ft)
50 (164ft)
10 (33ft)
15 (49ft)
20 (66ft)
20 (66ft)
25 (82ft)
90°
Oblique Rough Warped
DO NOT DEFORM PIPE WHILE
CUTTING
Be extra careful not to damage, dent, or
deform the pipe while cutting. This will
drastically reduce the heating efficiency of
the unit.
10 (33ft)
20 (66ft)
25 (82ft)
5 (16ft)
8 (26ft)
10 (33ft)
8 (26ft)
10 (33ft)
Page 15-GB

Hide quick links:

Publicidad

Tabla de contenido
loading

Tabla de contenido