I/O CONNECTIONS

CABLE INSTALLATION

Three 1/2" conduit knockouts are provided on the bottom of the
Pentair Pentek Intellidrive ® Constant Pressure Pump Controller
enclosure for the I/O wires.
Break out the closest 1/2" knockout and route the wires through.
Use a cord grip to prevent the wire from rubbing and causing a
short.
Never run low voltage I/O wire through the same conduit hole
NOTE:
as the 230V input wires or motor wires.
To connect the external wires to the terminals:
1.
Strip wire ½ inch
2.
Push spring terminal up with finger or slotted screwIntellidriver
3.
Insert wires from bottom
4.
Release spring terminal

CONNECTION EXAMPLES

Figures 15-18 show various connection schemes for typical
applications. Table 6 describes each I/O terminal, including purpose
and rating.
Figure 15 - Input with Internal 24 Volt Supply
+
115 VAC
or
230 VAC
-
Figure 16 - External Input with External Supply
PN957 (25-06-20)
Figure 17 - Output Relay with Internal 24 Volt Supply
6540 0412
6541 0412
6542 0412