Electrical
Nameplate
Motor HP
Volts
1/2
115
1/2
230
wire before connecting power supply wires. Use the wire size (including
the ground wire) specified in the wiring chart. If possible, connect the
pump to a separate branch circuit with no other appliances on it.
WIRING CONNECTIONS
damage the motor and voids the warranty. The supply voltage must be
within ±10% of the motor nameplate voltage.
NOTICE: The motor is factory wired for 115 volts. If necessary, reconnect
the motor for 230 volts, as shown in Figures 9A, 9B, and 9C. Do not
attempt to operate the pump as it comes from the factory on 230 volts.
Install, ground, wire, and maintain your pump in compliance with the
National Electrical Code (NEC) or the Canadian Electrical Code (CEC), as
applicable, and with all local codes and ordinances that apply. Consult
your local building inspector for code information.
Connection Procedure:
Step 1. Connect the ground wire first as shown in Figure 8. The ground
Step 2. There must be a solid metal connection between the pressure
Step 3. Connect the ground wire to a grounded lead in a service panel, to a
Step 4. Connect the power supply wires to the pressure switch as shown in
You have just completed the wiring for your pump.
Please go to Page 9 or 10 for startup preparations.
Wiring Chart – Recommended Wire and Fuse Sizes
Branch Fuse
Amps
Rating Amp
7.0
15
3.5
15
Hazardous voltage. Can shock, burn, or kill. Connect ground
Explosion hazard. Do not ground to a gas supply line.
Fire hazard. Incorrect voltage can cause a fire or seriously
wire must be a solid copper wire at least as large as the power
supply wires.
switch and the motor for motor grounding protection. If the pres-
sure switch is not connected to the motor, connect the green
ground screw in the switch to the green ground screw under the
motor end cover. Use a solid copper wire at least as large as the
power supply wires.
metal underground water pipe, to a metal well casing at least ten
feet (3M) long, or to a ground electrode provided by the power
company or the hydro authority.
Figure 8.
DISTANCE IN FEET FROM MOTOR TO SUPPLY
0 - 50
51 - 100
101 - 200
14 (2)
14 (2)
14 (2)
14 (2)
201 - 300
301 - 400
AWG WIRE SIZE (mm
12 (3)
10 (5.5)
10 (5.5)
14 (2)
14 (2)
8
401 - 500
2
)
8 (8.4)
14 (2)
14 (2)