5 LCS-Tool
5.2.10 Changing of Inverter
Parameters
FNN Note
In Germany, according to FNN note "Connecting
and operating storage units in low voltage networks"
(October 2016), systems eligible under the FIT
scheme in accordance with EEG and KWKG are not
allowed to feed energy from storage units into the
utility grid. To ensure this, the input value for
Discharge Setpoint/Consumption Limit is not
allowed to be negative.
Figure 26: LCS-Tool - changing of inverter parameters
All inverter parameters are Grid Guard protected and
require the Grid Guard code for changes. To change the
inverter settings, use your SMA Grid Guard code under the
user group Installer (see Section 5.2.2, page 19).
Procedure:
1. Open the LCS-Tool.
2. Log in as an Installer.
3. Call up the menu Setup.
4. Enter the respective values under Inverter
Parameter.
5. Select [Save] to save the changes.
28
IMVIOBOX-IA-xx-17
Deactivating/Activating the inverter
parameters
To activate and deactivate a parameter, double-click on the
parameter using the left mouse button.
When the parameters are activated, the input fields and
buttons are enabled. Inactive parameters are marked with
disable.