Test point light
To switch the test point light on or off, press the
■
L.H. key.
Continuity test
Place the test probes against the lead, fuse, etc.
■
to be tested.
3 At a resistance of 0 - 200 kΩ, the green "Rx/Ω"
LED lights up and an acoustic signal sounds.
FI/RCD trip test, PE (protective earth
test)
High current flow
Testing on moving and not perma-
Â
nently wired devices, extension leads,
etc. can, in the event of a fault, result
in a high current in metallic parts con-
nected to the protective conductor!
Only perform an RCD test on fixed
¾
installed systems and circuits.
To reduce interference effects, inductive and ca-
■
pacitive couplings during voltage testing, press
both FI/RCD buttons simultaneously.
3 A lower impedance is switched on.
3 The peak current is below 0.3 A (I
3 The additional load circuit is overload protect-
ed and reduces the load current after a few
seconds.
This integral load makes it possible to trigger an
RCD circuit breaker. The FI/RCD (max. 30 mA,
230 V/AC) is tested between phase and PE
conductor.
Hold a test probe against one phase conductor.
■
Hold the other test probe against the protective
■
conductor.
Press both FI/RCD buttons in as far as possible.
■
Note
Under normal circumstances the circuit
breaker is not normally triggered
without both the FI/RCD buttons being
pressed.
WARNING!
).
P
Maintenance/care
Keep the device always dry and clean. The
■
device may be cleaned using a damp cloth.
Battery change
If the batteries have become discharged, a warning
signal sounds and the device switches off.
Undo the battery compartment screws on the
■
main housing.
Open the battery compartment.
■
Change the batteries. Ensure the new batteries
■
are inserted with the correct polarity.
Close the battery compartment and screw the
■
lid in place.
Dispose of the empty batteries in an environmen-
■
tally compatible manner.
Environmental instructions
Do not dispose of this device with
normal household waste. Dispose of
the device via an approved waste
disposal company or via your local
authority waste disposal facility.
Observe the currently valid regula-
tions. In case of doubt, contact your
waste disposal facility. Dispose of all packaging in
an environmentally compatible manner.
Batteries:
Do not dispose of batteries in household waste,
do not expose to fire or water. Collect and recy-
cle batteries or dispose of with due care for the
environment.