4
Technical specifications
MPA...−ASI−8E8A−Z
General technical specifications
Protection class as per EN 60529
Electromagnetic compatibility
Protection against electric shock
(protection against direct and indirect
contact as per EN 60201−1 /IEC 204)
AS−Interface specifications
ID code
IO code
Profile
AS−Interface bus connection
Voltage range (protected against
incorrect polarity)
Residual ripple
max. current consumption
electronics (input circuitry
at 0−status incl. LED)
max. sum current for inputs
max. sum current for outputs
(valves incl. LED)
28
see Pneumatics manual
P.BE−MPA−...
IP65 (fully assembled)
tested to EN 50295
(low voltage switchgear)
with a PELV power unit
(Protected Extra Low
Voltage)
ID = F
H
IO = 7
H
S−7.F.E
DC 26.5
20 mVpp
< 25 mA
350 mA
MPA1: 540 mA
MPA2: 1065 mA
Festo VMPA−ASI−EPL−...−8E8A−Z 0705NH English
; ID1 = F
; ID2 = E
H
31.6 V
H