Warning
Use only power units which guarantee reliable electrical
isolation of the operating voltage as per EN 61558−2−6
with at least 4 kV isolation resistance (Protected Extra−
Low Voltage, PELV). Switch power packs are permitted,
providing they guarantee reliable isolation in accord
ance with EN 60950/VDE 0805.
Use a closed−loop power unit
S
Avoiding electrostatic discharges and complying with
S
protection class IP54: Seal the unused connections
with the protective caps supplied.
For guaranteeing the function: Connect the MTR−DCI
S
only with the following cables (observe max. length):
Cables
Power supply cable
(max. 10 m)
Control cable
(max. 30 m)
Programming cable
(max. 2.5 m)
... for reference switch
Festo P.BE−K−MTR−DCI 0411NH English
24 V DC/ 6 A for MTR−DCI− 42−...
24 V DC/ 10 A for MTR−DCI−52−...
Accessories type ...
KPWR−MC−1−SUB−9HC−...
KES−MC−1−SUB−9HC−...
KDI−MC−M8−SUB−9−...
e.g. type SME−8F−.../SMT−8F or extension
cable type KM8−M8−...
Length [m]
2.5 / 5 / 10
2.5 / 5 / 10
2.5
21